Installation requirements 

  Select a location where the typical temperature and 

humidity of the measured gas can be sensed with the 
wind speed specified. 

  Make sure that the entire probe is immersed in the 

measured gas.  Also, make sure that airflow passes 
perpendicular to the side of the probe. 

  Leave adequate maintenance clearance in front of the 

housing cover. 

  When installing in steam-heating AHU, make sure the 

probe is not directly exposed to the high-temperature 
steam that exceeds the probe allowable operating 
condition. 

  When installing the probe pointing upward, do not allow 

dew condensation on the probe.  Otherwise, dew 
condensation stays on the grooves of the filter cap, 
causing measuring error (until it gets dried.). 

 

  CAUTION 

 

  Do not step on the product.  External force can 

damage the product. 

 

Installing Models HTY7903, HY7903 series 
(for general AHU duct insertion) 

1)  Prepare the dedicated mounting bracket. 

Attach the indicator label for mounting hole at the probe 
mounting position, and make a mounting hole on the 
duct. 

 

 

 

 

 

 

Figure 2.  Indicator label on the duct 

 

2)  Fix the mounting bracket onto the duct with M4 screws 

(supplied with the bracket), inserting packing between 
the duct and the bracket. (The side with longer 
protruding part needs to face outward. See Fig. 3.) 

 

 

 

 

 

 

Figure 3.  Mounting bracket on the duct 

3)  Cover the duct with an insulating material. (If the duct is 

already covered with it, partially remove the insulating 
material for the bracket.  Then, fill the clearance between 
the bracket and the duct with the insulating material after 
fixing the bracket.) 

 

 

 

 

 

 

 

Figure 4.  Duct and the mounting bracket  

covered with insulating material 

 

4)  Turn the main unit stopper 45 degrees (from ‘a’ to ‘b’ 

shown in Fig. 5) to unlock, and insert the probe of the 
main unit into the bracket as the main unit claws and the 
bracket slits match. 

 

 

 

 

 

 

 

 

Figure 5.  Mounting the main unit on the duct  

(with the mounting bracket) 

 

5)  Completely insert the probe into the duct.  Then, fix the 

probe and the bracket by turning the stopper 45 degrees 
(from ‘b’ to ‘a’ shown in Fig. 6) to lock. 

 

 

 

 

 

 

 

Figure 6.  Fixing the main unit on the duct 

(with the mounting bracket) 

Air flow 

Duct 

Indicator label 

Air flow 

Duct 

Packing 

Mounting 
bracket 

Air flow 

Insulating 
material 

Stopper 

 
Claw 

Main unit of 
Model HTY7903/
Model HY7903 

a

b

45

°

b a 

Содержание HTY7903T

Страница 1: ...t is suitable for various applications such as a duct or chamber for building air conditioning and outdoor air measurement as well as industrial applications Model HY79X3 series for dewpoint temperatu...

Страница 2: ...is necessary to minimize lightning damages to the product Always disconnect power source before performing any wiring to prevent equipment damages Use crimp terminal lugs with insulation for electric...

Страница 3: ...Model number Description Insertion length HTY7903T1P00 Dewpoint temperature 1 5 V temperature Pt100 Long HTY7903T4P00 Dewpoint temperature 4 20 mA temperature Pt100 Long HTY7903T6P00 Dewpoint tempera...

Страница 4: ...0 Power consumption Models HTY79X3T1 HY79X3T1 series with 1 5 V output Models HTY79X3T4 HY79X3T4 series with 4 20 mA output Models HTY79X3T6 HY79X3T6 series with 0 10 V output 0 7 VA for 24 V AC 600 m...

Страница 5: ...ls HTY7903 HY7903 series Models HTY7913 HY7913 series Mounting bracket Part No 83157235 001 Figure 1 Dimensions mm 70 247 6 A A 51 3 45 6 67 3 113 5 110 20 70 108 6 51 3 45 6 67 3 113 5 110 20 30 25 5...

Страница 6: ...t Figure 2 Indicator label on the duct 2 Fix the mounting bracket onto the duct with M4 screws supplied with the bracket inserting packing between the duct and the bracket The side with longer protrud...

Страница 7: ...nel with the mounting bracket 4 Completely insert the probe into the panel Then fix the probe and the bracket by turning the stopper 45 degrees from b to a shown in Fig 10 to lock Figure 10 Fixing the...

Страница 8: ...seal connector connection Figure 16 Tightening the seal connector Figure 17 Connection of 7 and 4 core cables to terminals CAUTION Make sure all the wires are tightly connected to prevent heat generat...

Страница 9: ...19 Correct wiring separate 24 V AC transformers 24 V DC Transformer shared with two sensors Fig 20 shows wiring example of Model HY78X3T For connecting terminals and E 3 and 2 use power with 0 022 F...

Страница 10: ...oint single point calibration Replace the sensor Filter replacement CAUTION Installation must be performed by qualified personnel in accordance with all applicable safety standards IMPORTANT Be sure n...

Страница 11: ...le measuring instrument for single point calibration with correct procedure in appropriate environment Calibrated digital multimeter is recommended to check output Figure 26 Single point calibration M...

Страница 12: ...AB 5963 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Sep 2015 AB 5963 J AI 5963 Rev 5 2 Printed in Japan 12...

Отзывы: