background image

1

CP-UM-5306E

Control Motor 

Model ECM3000

 

User’s Manual

Thank you for purchasing an Azbil Corporation product.
This manual contains information for ensuring the correct 

use of this product. This manual should be read by those who 

design and maintain equipment that uses this product.
Be sure to keep this manual nearby for handy reference.
Please read “Terms and Conditions” from the following URL 

before ordering and use. 

https://www.azbil.com/products/factory/order.html

NOTICE

Be sure that the user receives this manual before the product is 

used.

Copying or duplicating this user’s manual in part or in whole is 

forbidden. The information and specifications in this manual are 

subject to change without notice.

Considerable effort has been made to ensure that this manual is 

free from inaccuracies and omissions. If you should find an error or 

omission, please contact the azbil Group.

In no event is Azbil Corporation liable to anyone for any indirect, 

special or consequential damages as a result of using this product.

SAFETY PRECAUTIONS

Safety precautions are for ensuring safe and correct use of 

this product, and for preventing injury to the operator and 

other people or damage to property. You must observe these 

safety precautions. Also, be sure to read and understand the 

contents of this user’s manual.

If this device is used in a manner not specified by the 

manufacturer, its built-in protective functions may be 

impaired.

l

 Key to symbols

WARNING

Warnings are indicated when mishandling this prod-

uct might result in death or serious injury to the user.

CAUTION

Cautions are indicated when mishandling this prod-

uct might result in minor injury to the user, or only 

physical damage to this product.

 WARNING

Before doing other wiring work, connect the frame 

ground terminal to ground. The ground connection 

should have a resistance of 100 Ω or less. Afterwards 

connect the other circuits.
Before removing, mounting, or wiring this device, be 

sure to turn off the power to the device and all connected 

devices. Failure to do so may cause electric shock.
Do not touch electrically charged parts such as the 

power terminals. There is a risk of electric shock.

 CAUTION

In order to use this product correctly, be sure to follow 

this manual, the manuals for any associated devices 

and equipment.
Installation, wiring, inspection, adjustment, maintenance, 

etc., should be carried out only by trained and experi-

enced technicians who have knowledge and technical 

skills related to this device and associated equipment.
Be sure to use this device correctly, within the ranges 

specified in this user’s manual. Otherwise device fail-

ure or malfunction could result.
Avoid installing the device where it will be subject to 

conditions such as the following. Otherwise device fail-

ure could result.

•  Certain chemicals, corrosive gases, or salt

•  High temperatures

•  Prolonged vibration

•  Direct sunlight
Do not stand on this device or use it as a step.

Doing so could damage the device, and if you lose your 

footing you may be injured.
Wire this device properly according to indoor wiring 

standards, technical standards, etc., using the types of 

wire and wiring methods specified in the user’s manual.

Otherwise, device failure or malfunction could result.
The motor part of this device can reach a high tempera-

ture during operation. There is a risk of burns if the 

cover is opened and the motor is touched immediately 

after the power has been turned off.
While power is being supplied and during operation, do 

not touch any movable part. Doing so may cause injury.
If equipment safety may be endangered by the failure 

of this device, consider having a fail-safe design for the 

system as a whole, with circuit breakers, duplexed con-

trollers, and limiter; or use a redundant design.
When discarding this device, dispose of it properly as 

industrial waste, following local regulations.

WARNING SYMBOLS USED FOR THE PRODUCT

To reduce the risk of an electric shock. resulting in 

personal injury, and to ensure safe operation of de-

vices, follow all safety notices in this document.
This symbol warns the user when there is a danger 

of electric shock from accidental contact.
This symbol on the motor warns the user that there 

is a danger of burns from accidental contact.

UNPACKING

Check the following items when removing the ECM3000 from its 

package:

  Name 

Part No. 

Q’ty  Remarks

•  Upset head bolt with captive washer 

 

395-106-25A 

4  M6 size

•  label 

[0]

,

[100]

 83165267-001  1 0(fully closed) and 100(fully open)

•  User’s Manual  CP-UM-5306JE  1  This Manual

OVERVIEW

ECM3000 control motors are designed to control various types of 

industrial equipment.

There are two types of strokes: a 90° stroke for burner control and 

a 160° stroke for valve control using hot and cold water, steam, 

etc. There are three types of control signal inputs: relay contact, 

4–20 mA DC, and potentiometer (nominal 135 Ω resistance input).

24, 100, and 200 V AC models are available. Flexible 85–264 V AC 

powered models are also available for 4–20 mA DC signal input 

models. The included bracket can be used for replacement of an 

older Azbil Corporation motor with this one.

Содержание ECM3000 Series

Страница 1: ...d technical skills related to this device and associated equipment Be sure to use this device correctly within the ranges specified in this user s manual Otherwise device fail ure or malfunction could...

Страница 2: ...ive load including inrush current with forced open close function 6 8 1 GB compliant models are not compliant with UL or CE standards 2 Direct reverse operation can be switched and zero point span and...

Страница 3: ...erminal is properly grounded 100 max using at least 2 mm2 wire and M4 crimp terminals with insulating sleeves During wiring open a knockout hole 22 mm dia on either side and pull out the cables from t...

Страница 4: ...ometer of the ECM3000F is a com bination resistor consisting of two different resistors con nected in parallel Accordingly the angle of rotation of the ECM3000F is pro portional not to the resistance...

Страница 5: ...ter AUXILIARY SWITCH OPTIONAL Adjustment z z Operating point An auxiliary switch can turn on if the arrow on the setting dial A B C or D is aligned with the mark The operating point can be set in a ra...

Страница 6: ...positioned within the scale 5 Turn the auxiliary switch unit counterclockwise until it clicks 6 Align the holes on the terminal block bracket with the holes on the chassis 7 Insert and tighten the 2 s...

Страница 7: ...e cable diameter 7 to 9 mm Material Case Die cast aluminum Cover Glass containing polycarbonate resin Bracket Steel Installation location Indoors Altitude 2000 m max Pollution degree 3 Mass Approx 3 k...

Страница 8: ...e like z z Auxiliary switch Item Specifications Auxiliary switches 4 or 2 Contact rating Standard model 250 V AC 100 mA to 5 A resistive load 100 mA to 3 A inductive load Low current model 250 V AC 1...