AB-6256 

 

Specifications/Instructions

 

Insertion Type CO

2

 Concentration Transmitter 

Model CY8100C1000 (Main Unit) 

Part No. 83165722-002 (Assembly Kit) 

 
General 

Model CY8100C in combination with Part No. 83165722-002 
is an insert type CO

2

 concentration transmitter used for 

detecting concentration of carbon dioxide (CO

2

) in ducts. 

This product can be used in a wide range of applications 
such as monitoring of CO

2

 concentration in return ducts and 

the control of outdoor air intake. 

 
Features 

 

Non-dispersive infrared absorption method (NDIR) 

 

Linear output signal in 1-5 V DC range 

 Long-term 

stability 

 
Model Number and Part Number 

For the insertion type CO

2

 concentration transmitter, both of 

the following items are required. 

Model/Part number 

Description 

CY8100C1000 Main 

unit 

83165722-002 Assembly 

kit 

 - Sampling probe 
 - Gasket, 2 screws, 2 washers 
 - Cable assembly 

 

 
 
 
 
 
 

 

 

 

 

 

 
Optional Parts 

Part number 

Description 

83165722-002 Assembly 

kit 

(for 

replacement) 

 - Sampling probe 
 - Gasket, 2 screws, 2 washers 
 - Cable assembly 

83104511-001 

Zero calibration service bag 
(CO

2

 zero calibration gas generator) 

83104981-001 

Zero calibration service cylinder 
(CO

2

 zero calibration gas cylinder) 

 

Specifications 

(1/2)

 

Item Specification 

Measuring range 

0 to 2000 ppm CO

2

 Concentration 

Operating 

principle 

Non-dispersive infrared absorption 
method (NDIR) 

Measuring accuracy 

±

 (50 ppm + 5 % of reading) 

Drift Continuously 

ON: 

±

150 ppm/year 

Continuously OFF (reference value): 
  

±

15 ppm/48 hours at 50 %RH 

Time constant 

15 min. or less (windless) 
3 min. or less (0.6 m/s wind) 

Operation CO

2

 concentration: 0 to 2000 ppm 

Temperature: 0 to 50 °C 
Humidity: 0 to 95 %RH (non-condensing)

Environmental  
conditions 

Transport/
Storage 

Temperature: -20 to 50 °C 
Humidity: 0 to 95 %RH (in moisture-
proof package) 

Power supply voltage 

24 V AC 

±

 10 %, 50 to 60 Hz 

Power consumption 

Max. 3 VA 

Output signal 

1 to 5 V DC (linear with 0-2000 ppm 
CO

2

 concentration) 

Allowable load resistance  5 k

Ω

 or more 

Wiring 

Power supply: 2-wire 
CO

2

 concentration output: 2-wire 

 

(2/2) 

Item Specification 

Initial stabilizing time 

Continuously OFF for 48 hours or longer: 
Approx. 10 days (

 Product in a 

package is exceptional.) 
Other than the above: Approx. 3 days

Allowable vibration 

4.9 m/s

2

 (10 to 150 Hz) 

Insulation resistance 

100 M

Ω

 or higher at 500 V DC 

(between the case and each lead wire)

Enclosure rating (main unit) IEC IP65 (dust-proof and water-proof)
Weight Approx. 

350 

Material Main 

unit 

 - Case: PC + ABS plastic  
             (Bayblend

®

 FR90) 

 - Cover: PC Makrolon

®

 6555 

Sampling probe: PC Makrolon

®

 6555

Application Indoor 

duct, 

chamber 

 

Содержание CY8100C1000

Страница 1: ...cylinder Specifications 1 2 Item Specification Measuring range 0 to 2000 ppm CO2 Concentration Operating principle Non dispersive infrared absorption method NDIR Measuring accuracy 50 ppm 5 of reading...

Страница 2: ...damages This product must be operated within its rated operating ranges specified in this manual Failure to comply will cause equipment damage All wiring must comply with local codes of indoor wiring...

Страница 3: ...mensions of the main unit with sampling probe mm Assembly kit Sampling probe Cable assembly Figure 2 Dimensions of the assembly kit mm 4P connector shows the mounting orientation 4 4 25 28 28 Mounting...

Страница 4: ...er is supplied Assembly The assembly kit sampling probe and cable assembly and the main unit must be ordered and mounted separately to minimize the drift See the above Precautions for installation sec...

Страница 5: ...robe by snap in bayonet mount Refer to the following procedure 1 Engage the notches of the main unit with the locking knobs of the sampling probe then lightly press the main unit 2 Turn the main unit...

Страница 6: ...it 10 cm away from the main unit Check that the reading on the LCD and the output ascend quickly LCD indication On the LCD CO2 concentration is continuously displayed The display is changed a when a b...

Страница 7: ...main unit Use either one 3 Turn on the zero calibration service bag to start supplying CO2 zero gas to the main unit 4 Keep supplying the CO2 zero gas until CO2 concentration is stabilized approximat...

Страница 8: ...en the power is turned on or during the normal operation is detected and indicated with the yellow LED and the too icon on the LCD as shown in Fig 11 Figure 11 Tool icon on the LCD If error code excep...

Отзывы: