Azbil CY8100C1000 Скачать руководство пользователя страница 6

AB-6256 

Wires Connection 

Connection of power supply line 

IMPORTANT: 
 

Do not apply power supply voltage other than 24 V AC.  Otherwise, it may damage the product. 

 

Use insulation transformer.  Do not share the 24 V AC power supply with any other device.  If the transformer is shared, a loop 
will formed at common and the product may get damaged.  Refer to the following examples. 

Shared transformer: 

Incorrect

 example   

 

         Separate transformer: 

Correct

 example 

 

 

 

 

 

 

 

 

        Loop is formed at the common line.   

 

 

   Loop is not formed at the common line. 

Figure 7.  Connection examples: with shared transformer and with separate transformers 

 

Terminals layout 

 

 

 

 

 

 

 

 
 

 

Figure 8.  Terminals arrangement 

 

 

Operation 

Operation check 

Remove the front cover of the main unit, and breathe directly onto it 10 cm away from the main unit.  Check that the reading on 
the LCD and the output ascend quickly. 

 

LCD indication 

On the LCD, CO

2

 concentration is continuously displayed.  The display is changed a when a button is pressed, as shown in Fig. 

10.  For the layout of each button, see Fig. 9. 
In the event of equipment trouble, tool icon is displayed on the LCD, as shown in Fig. 11. 

 

LED indication 

Green LED: Normal operation 

Yellow LED: Initializing, pressing a button, error during calibration 

 

 

24 V AC 

Multi-loop 

controller 

CO

concentration 

transmitter 

Shared 

common line

CO

concentration 

transmitter 

 

 

 

 

24 V AC 

Multi-loop 

controller

24 V AC 

 

+

 

-

 

 

+

 

-

 

UP

BR WH Y 

GR 

 Lead wires of the main unit cable 

Lead color 

Description 

WH: White 

24 V AC power (common) 

BR: Brown 

24 V AC power 

GR: Green 

Common output (-) 

Y: Yellow 

1-5 V DC output (+)  

 

Lead wires of the cable assembly 

Lead color 

Description 

White 

24 V AC power (common) 

Brown 24 

AC 

power 

Green Common 

output 

(-) 

Yellow 

1-5 V DC output (+)  

Содержание CY8100C1000

Страница 1: ...cylinder Specifications 1 2 Item Specification Measuring range 0 to 2000 ppm CO2 Concentration Operating principle Non dispersive infrared absorption method NDIR Measuring accuracy 50 ppm 5 of reading...

Страница 2: ...damages This product must be operated within its rated operating ranges specified in this manual Failure to comply will cause equipment damage All wiring must comply with local codes of indoor wiring...

Страница 3: ...mensions of the main unit with sampling probe mm Assembly kit Sampling probe Cable assembly Figure 2 Dimensions of the assembly kit mm 4P connector shows the mounting orientation 4 4 25 28 28 Mounting...

Страница 4: ...er is supplied Assembly The assembly kit sampling probe and cable assembly and the main unit must be ordered and mounted separately to minimize the drift See the above Precautions for installation sec...

Страница 5: ...robe by snap in bayonet mount Refer to the following procedure 1 Engage the notches of the main unit with the locking knobs of the sampling probe then lightly press the main unit 2 Turn the main unit...

Страница 6: ...it 10 cm away from the main unit Check that the reading on the LCD and the output ascend quickly LCD indication On the LCD CO2 concentration is continuously displayed The display is changed a when a b...

Страница 7: ...main unit Use either one 3 Turn on the zero calibration service bag to start supplying CO2 zero gas to the main unit 4 Keep supplying the CO2 zero gas until CO2 concentration is stabilized approximat...

Страница 8: ...en the power is turned on or during the normal operation is detected and indicated with the yellow LED and the too icon on the LCD as shown in Fig 11 Figure 11 Tool icon on the LCD If error code excep...

Отзывы: