Chapter 4. Explanation of Operation
z
Normal operation (Non-recycling oil-fired combustion (2-level combustion))
Input
AUR890 operation
Sequence
codes
Operation of external devices
Power ON
When approximately 8 seconds have passed after the power has been
turned on, the 7-segment LED display on the front panel of the AUR890
shows the sequence code [- -].
- -
Burner
operation
switch ON
- -
When the burner operation switch is turned
on, the blower starts to operate, and if the
limit and interlock conditions are normal, a
pre-purge is done. After the pre-purge, the
pre-purge completion signal is turned ON.
Blower: operating
External
controller
ON
If the pre-purge completion signal is ON and the external controller is
ON, the internal circuits are checked during the start check.
P
1
Afterward a false flame check is conducted during the ignition wait
time.
P3
If the status is normal, the safety lockout time begins, relays K1, K2, K3
and K5 turn ON, the ignition transformer starts, and the fuel oil valve
opens.
P4
Ignition transformer : start
Fuel oil valve : open
After the lockout time has passed, if a flame signal is detected, the
ignition transformer output is maintained until the standby time for
normal combustion has passed.
P5
Ignition transformer : continues operation
Fuel oil valve : remains open
When the flame sensor detects the flame from the fuel oil valve fuel,
relay K5 turns OFF, the ignition transformer stops, relay K4 turns ON, the
two-level fuel oil valve opens, and normal combustion begins.
The FLAME LED (green) on the front panel of the AUR890 lights up.
P8
Ignition transformer : stop
Two-level fuel oil valve : open
Burner
operation
switch OFF
When the burner operation switch is turned OFF, relays K1, K2, K3 and
K4 turn OFF, and the fuel oil valve and two-level fuel oil valve close.
The FLAME LED (green) on the front panel of the AUR890 turns off.
- -
Fuel oil valve : closed
Two-level fuel oil valve : closed
Blower : stop
Power OFF When the power is turned OFF, the 7-segment LED display on the front
panel of the AUR890 stops showing the sequence code [- -].
––
P1
––
––
Stop
Star
t check
P3
Ignition standb
y
P4
Lock
-out timing
P8
Main bur
ner c
ombustion standb
y
P5
Main bur
ner c
ombustion
Stop
Fuel oil valve
AUR890
Two-level fuel oil valve
Pre-purge time
(external circuit)
Start check + Ignition standby time
Approximately 3 s
Approximately 8 s
Lock-out timing time
Main burner combustion standby time
[Input]
Power supply
[7-segment display]
Limit, Interlock
[Output]
Ignition transformer
Burner operation switch
Blower
Controller
Combustion signal
Reset switch
[LED]
FLAME LED (Green)
Warning output
ALARM LED (Red)