3
Chapter 1. Overview
Model number
(Note: The dedicated sub-base and sideboard are not provided with the AUR890 controller. Order them separately.)
Model number
Power supply
Lock-out timing
Flame failure
response timing
Compatible flame detector
AUR890F110
100 Vac
13.5 ± 1.5 s
1 s max. *1
Flame rod (Ionization)
AUR890F130
100 Vac
13.5 ± 1.5 s
3 ± 1 s *1
Flame rod (Ionization)
AUR890F210
200 Vac
13.5 ± 1.5 s
1 s max. *1
Flame rod (Ionization)
AUR890F230
200 Vac
13.5 ± 1.5 s
3 ± 1 s *1
Flame rod (Ionization)
AUR890G130
100 Vac
13.5 ± 1.5 s
3 ± 1 s *2
UV sensor (AUD100/110/120)
AUR890G230
200 Vac
13.5 ± 1.5 s
3 ± 1 s *2
UV sensor (AUD100/110/120)
*1 Flame voltage at 2Vdc
*2 Flame voltage at 3Vdc
Related equipment
z
Compatible flame detector (sold separately)
•
Flame detector UV sensor
Model number
Name
Notes
AUD15C1000
Advanced UV sensor
Tube unit
Use a dedicated socket for the AUD100C/110C/120C
AUD100C100_
Advanced UV flame detector (Lead wire model
without AUD15C)
AUD15C1000, sold separately
AUD100C1000-A15 Advanced UV flame detector (Lead wire model
with AUD15C)
AUD15C1000 in package
AUD110C100_
Advanced UV flame detector (Terminal block
model without AUD15C)
AUD15C1000, sold separately
AUD110C1000-A15
Advanced UV flame detector (Terminal block
model with AUD15C)
AUD15C1000 in package
AUD120C120_
Advanced UV flame detector (1/2-inch
mounting model)
Without G1/2 adapter, AUD15C1000, sold separately
AUD120C121_
With G1/2 adapter, AUD15C1000, sold separately
_ : The box stands for one of the following codes. 0: standard product. D: with inspection record (with data).
T: tropicalization (AUD110C only). B: with inspection record (with data) and tropicalization (AUD110C only).
•
Flame rod
Model number
Name
Notes
C7007A
Flame rod holder
C7008A
Flame rod assembly
z
Optional parts (sold separately)
Model number
Product name
Notes
BC-R05A100
Dedicated sub-base
Required for AUR890
81447514-001
Connector for front wiring *
Contains one
Weidmueller model number : BL3.5/11F
Compatible wire: 0.2–1.5 mm
2
(28–14 AWG)
81447514-002
Connector for front wiring *
(for right-side wiring)
Contains one
Weidmueller model number : BL3.5/11/270F
Compatible wire: 0.2–1.5 mm
2
(28–14 AWG)
81447515-001
Side boards (2)
Contains two
Not included in the sub-base
Q890A100
Base unit for RA890 replacement
The mounting holes and terminal numbers are the same
as those of the sub-base (Q270A1024) of the RA890.
FSP136A100
Analog flame meter
81447519-001
Jack cover
Contains one
81447531-001
Front connector cover
Mounting screw supplied
* Used for flame voltage measurement.
Содержание AUR890 Series
Страница 58: ...50...
Страница 59: ...Revision History of CP SP 1380E Printed Edn Revised pages Description Feb 2015 1...