Chapter 4. Explanation of Operation
Alarms and combustion sequence
Name
Code
Interlock
error
False
flame
UV alarm Ignition
failure
Flame
failure
E0
E
1
E2
E6
E7
Stop
-
-
Start check
P
1
Ignition trial
P4
Pilot only / Hi
solenoid valve
ignition standby
P5
Main trial / Hi
solenoid valve
ignition
P6
Run
P8
Blank: Not monitored,
: Monitored
Instantaneous power failure or instantaneous voltage drop during operation
If an instantaneous power failure or instantaneous voltage drop occurs during
operation, this device operates as described below.
Instantaneous
power failure
Shorter than
50 ms
Operation continues
50 ms or
longer
Operation continues or restarts from stop, or
restarts after power-OFF
Instantaneous
voltage drop
(drop in power of
50 %)
Shorter than
100 ms
Operation continues
100 ms or
more
Operation continues or flame is extinguished due to
voltage drop in the flame detector*
* Because the voltage to the fuel valve also drops, fuel supply may decrease, causing the
flame to be extinguished.