AB-6880 

Measuring range and accuracy 

IMPORTANT: 
  Flow measuring accuracy shown in the below is for the valve sensor measuring 7 to 17 

°

C and 45 to 65 

°

ranges, 0.1 to 0.8 MPa pipe pressure, and 0.03 to 0.3 MPa differential pressure. Without these ranges, the flow 
rate measuring accuracy may lower. 

 

Item Specification 

Setting range 

Model number 

Nominal size

Cv value

Max. setting flow rate 

 

FVY5160J0011 

DN15 (1/2”) 

1.0 

10 l/min 

 

FVY5160J0012 

DN15 (1/2”) 

2.5 

25 l/min 

 

FVY5160J0013 

DN15 (1/2”) 

6.0 

60 l/min 

 

FVY5160J0021 

DN25 (1”) 

10 

100 l/min 

 

FVY5160J0022 

DN25 (1”) 

16 

160 l/min 

 FVY5160J0041 

DN40 

(1

1

/

2

”) 25 

250 

l/min 

 FVY5160J0042 

DN40 

(1

1

/

2

”) 40 

400 

l/min 

 

FVY5160J0051 

DN50 (2”) 

65 

650 l/min 

 FVY5160J0061 

DN65 

(2

1

/

2

”) 95 

950 

l/min 

 

FVY5160J0081 

DN80 (3”) 

125 

1250 l/min 

Flow rate measuring 

Measuring 
accuracy

 

(Factory preset)

Measuring  
range 

0 MPa to 1.0 MPa*

4

 

Pressure 
measuring 

Accuracy 

±

 0.5 %FS (factory preset)*

5

 

Measuring 
range 

°

C to 80 

°

Valve sensor*

3

 

Temperature  
measuring 

Accuracy 

±

 1.0 

°

C (factory preset)*

6

 

(within 0 

°

C to 80 

°

C measuring range, at -25 

°

C to 40 

°

C temperature difference between measuring 

temperature and ambient temperature) 

Measuring 
range 

°

C to 80 

°

Pipe 

Sensor*

7

 

Temperature 
measuring 

Accuracy 

±

 1 

°

C (factory preset)*

8

 

Notes: 

Δ

Pv is differential pressure between valve inlet pressure (Pvin) and outlet pressure (Pvout). 

2  Flow rate measuring accuracy above may change depending on the conditions including valve positions, differential pressure, etc. 

3  Valve sensor is the temperature and pressure sensors mounted onto the valve (Model FVY5160J), measuring valve surface temperature 

and inlet and outlet flow pressure. 

4  When you test the withstand pressure of the valve sensor manufactured on and after Nov. 1, 2011 (date code: 1144 or greater), up to  

1.6 MPa pressure can be applied to the valve sensor. 

5  The above pressure measuring accuracy is for the 7 

°

C to 65 

°

C flow temperature. If the flow temperature is out of the 7 

°

C to 65 

°

C range, 

the valve sensor flow measuring accuracy may lower. 

6  For accurate measuring of flow temperature, thermal insulation is required. Refer to the subsection 

Heat insulation

 for applying thermal 

insulation. 

7  Pipe sensor is the temperature sensor for pipe surface (ModelTY7820Z). 

8 For accurate measuring of flow temperature, thermal insulation is required. Refer to 

AB-6923 Specifications/Instructions of 

Temperature Sensor for Pipe Surface (Pt100 RTD)  Model TY7820Z

 

 
 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

 

 

 

       0 

10         20          30 

  40         50          60       70 

80        90        100 

DN15 
 Cv1.0, 

±

10 %RD

 Cv2.5, 

±

7 %RD 

 Cv6.0 

±

7 %RD 

 
DN25 to DN80 
 

 

±

5 %RD 

DN15 
 

±

3

 FS*

2

 

 
DN25-DN80
 

±

1

 FS*

2

 

300 

 
 

250 

 
 

200 

 
 

150 

 
 

100 

 
 

50 

 
 

Δ

Pv*

(k

Pa) 

Flow rate (%) 

Содержание ACTIVAL FVY5160J0011

Страница 1: ...ion Model FVY5160J communicates with a controller via SAnet Flow rate signal or position control signal is input from the controller and flow rate pressure temperature measuring signal and position si...

Страница 2: ...e product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Before wiring be sure to turn off the power to...

Страница 3: ...Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause overheating or fire Be sure to provide a circuit breaker for the power to the product as the product does...

Страница 4: ...odel VY516_J or Single Model MY804_A requires one SAnet address Figure 1 System configuration example SAnet connection in our BMS Building Management System BMS Infilex AC Model WY5117C Infilex GC Mod...

Страница 5: ...ed Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition...

Страница 6: ...0J0061 DN65 2 1 2 95 1 0 MPa Size Cv Close off rating FVY5160J0081 DN80 3 125 1 0 MPa Applicable fluid Chilled hot water Allowable fluid temperature 0 C to 80 C Non freezing Frozen process fluid aroun...

Страница 7: ...ion distance varies depending on the number of devices and the type of devices to be connected to For details regarding the transmission distance refer to Installation Manual of Intelligent Component...

Страница 8: ...suring Accuracy 1 C factory preset 8 Notes 1 Pv is differential pressure between valve inlet pressure Pvin and outlet pressure Pvout 2 Flow rate measuring accuracy above may change depending on the co...

Страница 9: ...m Seal connector for the cable gland Part No 83104346 014 Applicable wire size 9 mm to 11 mm Seal connector for the cable gland is necessary for IEC IP54 protection Cable gland with three ports Part N...

Страница 10: ...27 60 18 90 125 19 4 6 6 FVY5160J004X 40 241 103 165 82 5 20 105 140 19 4 10 0 FVY5160J0051 50 245 107 178 89 20 120 155 19 4 11 5 FVY5160J0061 65 262 124 190 90 22 140 175 19 4 16 0 FVY5160J0081 80 2...

Страница 11: ...ector for the Pipe sensor Service pin switch Port for the Pipe sensor cable Operation status LED 1 Flow rate status LEDs 4 Connector for Display Panel Terminal block Ground terminal Port for Display P...

Страница 12: ...es during installation Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product Install the valve to the pipe so that they are elect...

Страница 13: ...e the actuator in water Although Model FVY5160J can be used outdoors be sure not to expose Model FVY5160J to direct sunlight Provide the outdoor cover optional to install outdoors Install Model FVY516...

Страница 14: ...hed to the yoke Install a bypass pipe and gate valves on the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side Before activating Model FVY5160J fully op...

Страница 15: ...ally open close valve do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the valve slowly turn the joint If shock is sent to the actuator the actuator may get damaged...

Страница 16: ...tage e g 100 V AC 200 V AC to Model FVY5160J To prevent damage cover the terminals except when connecting disconnecting wires Do not leave any refuse including metal chips inside the actuator after cu...

Страница 17: ...ual of Intelligent Component Series for SAnet Communication AB 6713 To keep IP54 protection dust proof and splash proof Use a water proof connector for Model FVY5160J in a high humidity environment or...

Страница 18: ...ing wire colors of the Display Panel are also described in the Specifications Instructions of Display Panel AB 6922 If you use a different cable be sure to match the terminal numbers to connect the wi...

Страница 19: ...t addressing operation of Data Setter or PC MMI Then press the service pin switch Do not keep the switch pressed for longer than 5 seconds 3 Address will be set within 5 seconds after pressing the ser...

Страница 20: ...a clean location with no dust oil or moisture Attach the system indication label by pressing the whole surface of the label to stick on the product surface Operation Check in Manual Operation Mode In...

Страница 21: ...F Manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 1 25 second OFF Error during manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 0 25 second OFF...

Страница 22: ...onding actions shown in the table If your problem is not solved by the corresponding action please contact Azbil Corporation near you Table 3 Inspection items and details Inspection item Inspection in...

Страница 23: ...brates or produces an abnormal noise Insufficient air vent inside piping Primary Pvin pressure condition Differential pressure Pvin Pvout condition Take air out of piping Adjust the mounting position...

Страница 24: ...n other countries KPEV is a registered trademark of Furukawa Electric Co Ltd Specifications are subject to change without notice Building Systems Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN...

Отзывы: