Inspection and Troubleshooting 

 

WARNING 

 

  Detach the terminal cover only when wiring the product. Before detaching the terminal cover, be sure to turn off the 

power to the product and all the connected devices. After wiring, be sure to reattach the terminal cover.  
Failure to do so might cause electric shock. 

 

 

CAUTION 

 

  Do not carelessly touch the product when being used to control hot water. 

Its temperature becomes high, and you might get burned. 

 

 

Inspect Model FVY5160J according to Table 3. 

  Be sure to check the flow measuring accuracy according to 

Flow measuring accuracy

 in Table 3. Flow measuring 

accuracy is very essential for Model FVY5160J used for energy management, energy-saving application, etc.  
Install the Valve Sensor Diagnosis software in your client PC to inspect flow measuring accuracy. This software allows the 
client PC to automatically calculate differential pressure measuring accuracy. Note that optional Display Panel or our 
engineering tool (Data Setter/PC-MMI) is required for field inspection. 

 

Manually open/close valve at least once a month if it is left in inactive state for a long period. 

 

Visually inspect the fluid leakage of the valve and the actuator operations every six months. If any of the problems described 
in Table 4 are found, take corresponding actions shown in the table. 
If your problem is not solved by the corresponding action, please contact Azbil Corporation near you. 

 

Table 3.  Inspection items and details 

Inspection item 

Inspection interval 

Inspection detail 

Visual inspection 

Semiannual 

  Fluid leakage from the gland and the flange face 

 Loosened 

bolts 

  Valve and actuator damages 

Operating status 

Semiannual 

  Unstable open/close operation 

  Abnormal noise and vibration 

  Abnormal differential pressure across valve (Pvin-Pvout) in fully closed/open 

position. 

Routine inspection 

Any time 

  Fluid leakage to the outside 

  Abnormal noise and vibration 

  Unstable open/close operation 

 Valve 

hunting 

Flow measuring accuracy  Any time (annual) 

  Measuring accuracy of differential pressure across valve: 

Measure the valve inlet pressure and outlet pressure when they are equal and check 
the values measured by the valve sensor. If difference of the values is 

±

3 kPa, flow 

measuring accuracy satisfies the factory preset accuracy. 
Situation of inlet pressure equal to outlet pressure  

 No flow across the valve in open position 

    e.g,  when supply pump is OFF, or when hand valves on the inflow and/or outflow 
 

sides of the valve are/is fully closed. 

  Valve position detecting accuracy: 

Ask our salesperson/serviceperson for details. 

Note: 

Simplified inspection of flow measuring accuracy is illustrated above. For accurate inspection, a reference flow meter is required. Note that 
you cannot field-calibrate or field-adjust flow measuring accuracy. 

 

Содержание ACTIVAL FVY5160J0011

Страница 1: ...ion Model FVY5160J communicates with a controller via SAnet Flow rate signal or position control signal is input from the controller and flow rate pressure temperature measuring signal and position si...

Страница 2: ...e product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Before wiring be sure to turn off the power to...

Страница 3: ...Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause overheating or fire Be sure to provide a circuit breaker for the power to the product as the product does...

Страница 4: ...odel VY516_J or Single Model MY804_A requires one SAnet address Figure 1 System configuration example SAnet connection in our BMS Building Management System BMS Infilex AC Model WY5117C Infilex GC Mod...

Страница 5: ...ed Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition...

Страница 6: ...0J0061 DN65 2 1 2 95 1 0 MPa Size Cv Close off rating FVY5160J0081 DN80 3 125 1 0 MPa Applicable fluid Chilled hot water Allowable fluid temperature 0 C to 80 C Non freezing Frozen process fluid aroun...

Страница 7: ...ion distance varies depending on the number of devices and the type of devices to be connected to For details regarding the transmission distance refer to Installation Manual of Intelligent Component...

Страница 8: ...suring Accuracy 1 C factory preset 8 Notes 1 Pv is differential pressure between valve inlet pressure Pvin and outlet pressure Pvout 2 Flow rate measuring accuracy above may change depending on the co...

Страница 9: ...m Seal connector for the cable gland Part No 83104346 014 Applicable wire size 9 mm to 11 mm Seal connector for the cable gland is necessary for IEC IP54 protection Cable gland with three ports Part N...

Страница 10: ...27 60 18 90 125 19 4 6 6 FVY5160J004X 40 241 103 165 82 5 20 105 140 19 4 10 0 FVY5160J0051 50 245 107 178 89 20 120 155 19 4 11 5 FVY5160J0061 65 262 124 190 90 22 140 175 19 4 16 0 FVY5160J0081 80 2...

Страница 11: ...ector for the Pipe sensor Service pin switch Port for the Pipe sensor cable Operation status LED 1 Flow rate status LEDs 4 Connector for Display Panel Terminal block Ground terminal Port for Display P...

Страница 12: ...es during installation Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product Install the valve to the pipe so that they are elect...

Страница 13: ...e the actuator in water Although Model FVY5160J can be used outdoors be sure not to expose Model FVY5160J to direct sunlight Provide the outdoor cover optional to install outdoors Install Model FVY516...

Страница 14: ...hed to the yoke Install a bypass pipe and gate valves on the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side Before activating Model FVY5160J fully op...

Страница 15: ...ally open close valve do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the valve slowly turn the joint If shock is sent to the actuator the actuator may get damaged...

Страница 16: ...tage e g 100 V AC 200 V AC to Model FVY5160J To prevent damage cover the terminals except when connecting disconnecting wires Do not leave any refuse including metal chips inside the actuator after cu...

Страница 17: ...ual of Intelligent Component Series for SAnet Communication AB 6713 To keep IP54 protection dust proof and splash proof Use a water proof connector for Model FVY5160J in a high humidity environment or...

Страница 18: ...ing wire colors of the Display Panel are also described in the Specifications Instructions of Display Panel AB 6922 If you use a different cable be sure to match the terminal numbers to connect the wi...

Страница 19: ...t addressing operation of Data Setter or PC MMI Then press the service pin switch Do not keep the switch pressed for longer than 5 seconds 3 Address will be set within 5 seconds after pressing the ser...

Страница 20: ...a clean location with no dust oil or moisture Attach the system indication label by pressing the whole surface of the label to stick on the product surface Operation Check in Manual Operation Mode In...

Страница 21: ...F Manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 1 25 second OFF Error during manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 0 25 second OFF...

Страница 22: ...onding actions shown in the table If your problem is not solved by the corresponding action please contact Azbil Corporation near you Table 3 Inspection items and details Inspection item Inspection in...

Страница 23: ...brates or produces an abnormal noise Insufficient air vent inside piping Primary Pvin pressure condition Differential pressure Pvin Pvout condition Take air out of piping Adjust the mounting position...

Страница 24: ...n other countries KPEV is a registered trademark of Furukawa Electric Co Ltd Specifications are subject to change without notice Building Systems Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN...

Отзывы: