AB-6880
20
Table 1. Basic address setting of this product and other Intelligent Component Series devices
Add. Device
Sub-DO/AI
Sub-DI
1
Outdoor air damper
2
Exhaust air damper
3 Return
air
damper
4
Switch damper of total heat exchanger for outdoor air
5
Switch damper of total heat exchanger for exhaust air
6
Chilled/hot water valve / Chilled water valve
Filter alarm
8
Hot water valve (Chilled water valve*)
Humidifying ON/OFF
A (10) Humidifying valve
Notes:
∗
For ‘chilled/hot water valve + chilled water valve’ application, set address 6 for chilled/hot water valve and 8 for chilled water valve.
∗
Items in bold characters are the basic address to set for Model FVY5160J. Address 7 and 9 are the second addresses for Model FVY5160J
which requires two consecutive (first and second) addresses.
∗
The above list is a basic setting example. Set address and use sub-I/O in response to system configuration, installation location, and wiring
best suitable for your application.
∗
Addresses B (11) to F (15) are reserved.
System Indication Label
A part of the product code label can be a system indication label. Clip the part, and write down the name of the system, host
controller number of the system, SAnet line number, and address. Then attach the part, as the system indication label, to a
location where you can easily check.
Figure 17. System indication label
IMPORTANT:
•
Attach the system indication label to a clean location with no dust, oil, or moisture.
•
Attach the system indication label by pressing the whole surface of the label to stick on the product surface.
Operation Check in Manual Operation Mode
In the manual operation mode, even when this product has not been connected via SAnet yet, the operations shown in Table 2
can be performed and checked. Follow the procedure below for the operation check. For the locations of the service pin switch
and the rotary switch, see Fig. 15.
1) Press and hold the service pin switch for 10 seconds to enter the manual mode.
2) Turn the rotary switch to the desired position (See Table 2.), using a precision slotted screwdriver.
Table 2. Operations in the manual operation mode
Rotary switch scale
Operation
0
Restart (to go back to the normal operation mode).
1
Cancel forced open/close.
2
Fully close (in 0 % position).
3
Open in 25 % position.
4
Open in 50 % position.
5
Open in 75 % position.
6
Fully open (in 100 % position).
∗
Note:
Do not set the rotary switch to scales 7, 8, 9, A, B, C,
D, E, F. These scales are not available in the manual
operation mode.
Operation will start in 3 seconds after setting the rotary switch.
3) After the operation check, press and hold the service pin switch for 10 seconds to go back to the normal operation mode.
4) If the address is set with the rotary switch, be sure to reset the rotary switch at the address after entering the normal
operation mode.
System indication label
Clip and write down:
•
SYSTEM NAME:
System name or device number
•
CON No.:
Host controller number
(Infilex GC/Infilex GD number)
•
SAnet No.:
SAnet line number
•
ADDRESS:
Address