Azbil ACTIVAL FVY5160J0011 Скачать руководство пользователя страница 1

AB-6880 

 

Specifications/Instructions

Intelligent Component Series 

ACTIVAL

 Flow Measurement and Control Valve 

(JIS 10K / FC200) 

 

 
General 

ACTIVAL

 Flow Measurement and Control Valve Model 

FVY5160J is a series of motorized two-way valves with 
flanged-end connection. DN15 to DN80 rotary valve and 
actuator are integrated in a single unit. 

In combination with the functions of a control valve, Model 
FVY5160J measures and controls flow rate. Model 
FVY5160J thus enables to control temperature for air 
conditioning by controlling chilled/hot water volume and to 
measure chilled/hot water flow rate. 

For such a high functionality, compact size and simple 
installation of Model FVY5160J are incomparable. 

Model FVY5160J communicates with a controller via SAnet 
(proprietary protocol). 

 

 JIS: Japanese Industrial Standards 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

 

Compact and lightweight: 
Rotary valve actualizes small body and light weight. 

 

Valve and actuator integrated in a single unit. 

 SAnet 

communication: 

Model FVY5160J communicates with a controller via 
SAnet. Flow rate signal or position control signal is input 
from the controller, and flow rate, pressure, temperature 
measuring signal, and position signal are output to the 
controller. 

 

Valve for chilled/hot water control applicable to large Cv 
value, high rangeability, and low leakage. 

 

Durable actuator with low power consumption. 

 

Flow rate control/position control operation selectable: 
For flow rate control, flow characteristic is selectable 
(equal percentage or linear). For position control, flow 
characteristic is equal percentage. 

 

 

Sub-DI and sub-DO for wire saving: 
Sub-DI (digital input) and sub-DO (digital output) 
provided take signals, including humidifying output and 
differential pressure switch of neighboring devices, 
leading to wire saving. 

  In combination with Display Panel (optional) and the 

temperature sensor for pipe surface (optional), pressure, 
temperature, and flow rate can be displayed on the 
Display Panel. 

 

CE Marking certified product: 
Model FVY5160J conforms to all the applicable 
standards of CE Marking. 

 

 

 

 

IMPORTANT: 
 

Do not use the data measured by Model FVY5160J for charging or dealing purposes. 

 
 

Содержание ACTIVAL FVY5160J0011

Страница 1: ...ion Model FVY5160J communicates with a controller via SAnet Flow rate signal or position control signal is input from the controller and flow rate pressure temperature measuring signal and position si...

Страница 2: ...e product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Before wiring be sure to turn off the power to...

Страница 3: ...Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause overheating or fire Be sure to provide a circuit breaker for the power to the product as the product does...

Страница 4: ...odel VY516_J or Single Model MY804_A requires one SAnet address Figure 1 System configuration example SAnet connection in our BMS Building Management System BMS Infilex AC Model WY5117C Infilex GC Mod...

Страница 5: ...ed Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition...

Страница 6: ...0J0061 DN65 2 1 2 95 1 0 MPa Size Cv Close off rating FVY5160J0081 DN80 3 125 1 0 MPa Applicable fluid Chilled hot water Allowable fluid temperature 0 C to 80 C Non freezing Frozen process fluid aroun...

Страница 7: ...ion distance varies depending on the number of devices and the type of devices to be connected to For details regarding the transmission distance refer to Installation Manual of Intelligent Component...

Страница 8: ...suring Accuracy 1 C factory preset 8 Notes 1 Pv is differential pressure between valve inlet pressure Pvin and outlet pressure Pvout 2 Flow rate measuring accuracy above may change depending on the co...

Страница 9: ...m Seal connector for the cable gland Part No 83104346 014 Applicable wire size 9 mm to 11 mm Seal connector for the cable gland is necessary for IEC IP54 protection Cable gland with three ports Part N...

Страница 10: ...27 60 18 90 125 19 4 6 6 FVY5160J004X 40 241 103 165 82 5 20 105 140 19 4 10 0 FVY5160J0051 50 245 107 178 89 20 120 155 19 4 11 5 FVY5160J0061 65 262 124 190 90 22 140 175 19 4 16 0 FVY5160J0081 80 2...

Страница 11: ...ector for the Pipe sensor Service pin switch Port for the Pipe sensor cable Operation status LED 1 Flow rate status LEDs 4 Connector for Display Panel Terminal block Ground terminal Port for Display P...

Страница 12: ...es during installation Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product Install the valve to the pipe so that they are elect...

Страница 13: ...e the actuator in water Although Model FVY5160J can be used outdoors be sure not to expose Model FVY5160J to direct sunlight Provide the outdoor cover optional to install outdoors Install Model FVY516...

Страница 14: ...hed to the yoke Install a bypass pipe and gate valves on the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side Before activating Model FVY5160J fully op...

Страница 15: ...ally open close valve do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the valve slowly turn the joint If shock is sent to the actuator the actuator may get damaged...

Страница 16: ...tage e g 100 V AC 200 V AC to Model FVY5160J To prevent damage cover the terminals except when connecting disconnecting wires Do not leave any refuse including metal chips inside the actuator after cu...

Страница 17: ...ual of Intelligent Component Series for SAnet Communication AB 6713 To keep IP54 protection dust proof and splash proof Use a water proof connector for Model FVY5160J in a high humidity environment or...

Страница 18: ...ing wire colors of the Display Panel are also described in the Specifications Instructions of Display Panel AB 6922 If you use a different cable be sure to match the terminal numbers to connect the wi...

Страница 19: ...t addressing operation of Data Setter or PC MMI Then press the service pin switch Do not keep the switch pressed for longer than 5 seconds 3 Address will be set within 5 seconds after pressing the ser...

Страница 20: ...a clean location with no dust oil or moisture Attach the system indication label by pressing the whole surface of the label to stick on the product surface Operation Check in Manual Operation Mode In...

Страница 21: ...F Manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 1 25 second OFF Error during manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 0 25 second OFF...

Страница 22: ...onding actions shown in the table If your problem is not solved by the corresponding action please contact Azbil Corporation near you Table 3 Inspection items and details Inspection item Inspection in...

Страница 23: ...brates or produces an abnormal noise Insufficient air vent inside piping Primary Pvin pressure condition Differential pressure Pvin Pvout condition Take air out of piping Adjust the mounting position...

Страница 24: ...n other countries KPEV is a registered trademark of Furukawa Electric Co Ltd Specifications are subject to change without notice Building Systems Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN...