AB-7131
17
3) Unplug the 6-pin connector for temperature sensor (Pt100 input) from the actuator socket, and connect the sheath stripped
wires (3-core cable of the temperature sensor (Pt100 input)) to the connector.
Insert a slotted screwdriver (with 2.5
0.4 mm blade tip) into a square hole of the connector for clamp release. The
screwdriver successfully releasing the clamp remains the inserted position. Insert the stripped wire into a circular hole
(terminal), and then pull out the screwdriver
.
Make sure that all the wires are completely connected by lightly pulling the
wires.
Figure 16. Wires connection to the 6-pin connector for the temperature sensor
4) Plug the connector into the actuator socket.
Note:
Completely plug the connector into the actuator socket. Incompletely plugged connector might become unplugged due to vibration.
Wires connection of Display Panel
Figure 17. 4-pin connector for Display Panel
Terminal Wire
color*
Description
RED
Red
12 V DC
BLK Black
0
V
WHT White
AP-bus
(+)
GRN Green
AP-bus
(-)
Note:
Wire color of the Display Panel shown in the above table is the wire colors of the
recommended
cable.
1) Pass the 4-core cable of Display Panel through the actuator port for Display Panel. (See Fig. 3 for the location of the port.)
2) Strip the wire sheath. Strip length is 8 mm. (See Fig. 15.)
3) Unplug the 4-pin connector for Display Panel from the actuator socket, and connect the sheath stripped wires to the
connector. Hold down a clamp release button using a slotted screwdriver, insert the stripped wire into a terminal, and then
release the button. Make sure that all the wires are completely connected by lightly pulling out the wires.
Figure 18. Wires connection to the 4-pin connector for Display Panel
4) Plug the connector into the actuator socket.
Note:
Completely plug the connector into the actuator socket. Incompletely plugged connector might become unplugged due to vibration.
Wires connection of RS-485 communication
Figure 19. 6-pin connector for RS-485 communication
Terminal Description
In DA
DA
In DB
DB
In SG
SG
Out DA
DA
Out DB
DB
Out SG
SG
1) Pass the cable of RS-485 communication through the actuator wiring port (knockout).
2) Strip the wire sheath. Strip length is 7 mm.
DA DB SG
In
Out
DA DB SG
R B W G
R: RED
B: BLK
W: WHT
G: GRN
Insert a screwdriver.
Insert a wire.
Lightly pull
connected wires.
Hold down a button.
Insert a wire.
Lightly pull out
connected wires.