Azbil AB-7352-U Скачать руководство пользователя страница 4

AB-7352-U 

 

Model Numbers 

Model VY5198K00XXS-147/VY5198H00XXS-147 is the model for the valve and actuator integrated into a single unit.  
The model number label is attached to the yoke. The 4 to 20 mA control signal is indicated on the actuator label and on the wiring 
diagram. 

Base 

model 

number 

Actuator/valve Actuator Valve  

Fixed

Description 

Control 

signal 

Rating/ 

material 

Type 

 

Nominal 

size/Cv 

VY51 

 

 

 

 

 

 

Motorized two-way valve with flanged-end connection 

 

 

 

 

 

 

4 mA DC to 20 mA DC input with 4 mA DC to 20 mA DC feedback output 

 

 

 

 

 

 

ANSI Class125 equivalent / Gray cast iron* 

 

 

 

 

 

 

NEMA 4X and IEC IP54 protected and standard torque type spring return 
actuator with terminal block 
(Mountable valve sizes: 1

1

/

2

" to 3") 

 

 

 

 

 

 

NEMA 4X and IEC IP54 protected and standard torque type spring return 
actuator with terminal block 
for high differential pressure application 
(Mountable valve sizes: 2

1

/

2

” to 3") 

    

00 

 

 

 

    

 

41 

 

1

1

/

2

” / 25 Cv 

    

 

42 

 

1

1

/

2

” / 40 Cv 

 

 

 

 

 

51 

 

   2” / 65 Cv 

    

 

61 

 

2

1

/

2

” / 95 Cv 

 

 

 

 

 

81 

 

   3” / 125 Cv 

    

  

S-147 – 

* This product was designed and manufactured conforming to the ISO (International Organization for Standardization, PN16 / GG-20). 

 

 

Specifications 

For weight, refer to the table shown in the section 

Dimensions

 Valve specifications 

Item Specification 

Model 

Two-way valve with flanged-end connection, proportional control 

Body pressure rating 

ANSI Class125 equivalent (Max. working pressure: 230 psig) 
 
 

 

End connection 

ANSI Class125 Bolt pattern flanges, flat face flange (FF)

Size, Cv, Close-off ratings 
 
Note: 

Close-off ratings of the actuator in 
combination are shown on the right. 
Practical close-off rating required for the 
valve controlling 374 

F (175 

C) steam is 

116 psig. 

Model number 

Nominal size 

Cv 

Close-off ratings 

Inch DN 

Steam 

Chilled/hot water

High-temp. water

VY5198K0041S-147 1

1

/

2

” 

40 

25 

145 psig 

145 psig 

VY5198K0042S-147 1

1

/

2

” 

40 

40 

145 psig 

145 psig 

VY5198K0051S-147 

2” 

50 

65 

145 psig 

145 psig 

VY5198K0061S-147 2

1

/

2

” 65 95  43.5 

psig 

 

VY5198K0081S-147 3”  80 125

14.5 

psig 

 

VY5198H0061S-147

2

1

/

2

” 

65 

95 

145 psig 

102 psig 

VY5198H0081S-147

3” 

80 

125

102 psig 

58 psig 

Materials 

Body 

Gray cast iron 

Plug, stem 

Stainless steel 

Seat ring 

Heat-resistant PTFE 

Gland packing 

Inorganic fiber 

Gasket 

Non-asbestos joint sheet 

Applicable fluid 

Chilled/hot water, high-temperature water, steam 

Allowable fluid temperature 

32 

F to 347 

F (0 

C to 175 

C), non-freezing 

Flow characteristic 

Equal percentage 

Rangeability 

100 : 1 

Seat leakage 

0.01 % of rated Cv value 

Paint 

Gray 

Class125

(ASTM A126 class B ASME 16.1-2010)

Max working pressure 230 psig at 32 to 347 

Use the product within the hatched range. 

Содержание AB-7352-U

Страница 1: ...t water control and for steam control applicable to high differential pressure large Cv value high rangeability and low leakage Durable actuator with low power consumption Equal percentage flow charac...

Страница 2: ...e product might cause injury or product damage Detach the cover only when wiring setting the product or maintenance and reattach the cover after wiring setting the product or maintenance Failure to do...

Страница 3: ...the terminal screws might cause fire or overheating Do not touch the moving parts of the product Doing so might cause injury Dispose of this product as industrial waste in accordance with your local...

Страница 4: ...specifications Item Specification Model Two way valve with flanged end connection proportional control Body pressure rating ANSI Class125 equivalent Max working pressure 230 psig End connection ANSI...

Страница 5: ...Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition Limit operating condition Transport storage conditions packaged 2 Ambient tempe...

Страница 6: ...1 7 09 0 75 4 41 9 lb DN65 mm 314 124 190 90 20 140 180 19 19 kg VY5198K0081S 147 3 in 12 40 4 92 7 99 3 94 0 87 6 00 7 48 0 75 4 48 7 lb DN80 mm 315 125 203 100 22 152 4 190 19 22 1 kg Model VY5198H0...

Страница 7: ...AB 7352 U 7 Parts Identification Figure 2 Parts identification...

Страница 8: ...ication of the selector switches Figure 3 Selector switches Open close selector switch for input signal failure If no control signal is input the actuator automatically closes 0 or opens 100 the valve...

Страница 9: ...rrow indicated on the valve body Installation location CAUTION Do not install the product nearby a steam coil pressurized hot water coil or any high heat source High temperature radiation might cause...

Страница 10: ...position the valve and flush the pipes with the ACTIVAL installed at the maximum flow rate to remove all the foreign substances Factory preset position 0 For steam control drain retained water conden...

Страница 11: ...ept when connecting disconnecting wires Do not leave any refuse including metal chips after cutting a knockout hole and after connecting the wires inside the actuator Do not connect 24 V AC power to t...

Страница 12: ...terproof the wiring port For cable connection use a water proof connector Seal connector Part No 83104346 003 is recommended For conduit connection use a water proof plica tube or the like Terminals c...

Страница 13: ...transformer is required for ACTIVAL Transformer without isolation might damage the ACTIVAL and other devices connected to ACTIVAL Model SDC35 SDC36TC0 Model VY5198K VY5198H 4 to 20 mA DC input with 4...

Страница 14: ...Auxiliary switch Part No 83165274 001 Switches A and B actuating position Adjustable between 0 fully closed and 100 fully open Figure 11 Internal connection of Part No 83165274 001 OP1 OP2 OP3 N C N O...

Страница 15: ...es not operate at all Conditions of the power applied and of the input signal applied Loosened terminals Wiring condition disconnected wires Check the power supply and the controller connected to Tigh...

Страница 16: ...AB 7352 U Rev 4 0 Jun 2016 AB 7352 U 16 ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries...

Отзывы: