Inspection and Troubleshooting 

 

CAUTION 

 

  Do not carelessly touch this product when being used to control hot water or steam. The product temperature is 

hot, and you might get burned. 

 

 

Inspect the ACTIVAL according to Table 1. 

 

Manually open/close the ACTIVAL at least once a month if it is left in inactive state for a long period. 

 

Visually inspect the fluid leakage of the valve and the actuator operations every six months. If any of the problems described 
in Table 2 are found, take corresponding actions shown in the table. 
If your problem is not solved by the corresponding action, please contact Azbil Corporation near you. 

 

Table 1.  Inspection items and details 

Inspection item 

Inspection interval 

Inspection detail 

Visual inspection 

Semiannual 

  Fluid leakage from the gland and the flange face 

 Loosened 

bolts 

  Valve and actuator damages 

Operating status 

Semiannual 

  Unstable open/close operation 

  Abnormal noise and vibration 

Routine inspection 

Any time 

  Fluid leakage to the outside 

  Abnormal noise and vibration 

  Unstable open/close operation 

 Valve 

hunting 

 

Table 2.  Troubleshooting 

Problem 

Part to check 

Action 

Fluid leaks from the flange face. 

Loosened flange bolts 
Gasket on the flange face 
Misaligned piping 

Tighten the flange bolts. 
Replace the gasket. 
Redo piping. 

Fluid leaks from the gland part. 

 

Consult with our sales personnel. 

Fluid leaks from the bonnet. 

Loosened bolts 

Tighten the bolts. 

Valve does not operate smoothly / 
valve stops halfway / 
valve does not operate at all. 

Conditions of the power applied and of the input 
signal applied 
Loosened terminals 
Wiring condition / disconnected wires 

Check the power supply and the controller 
connected to. 
Tighten the terminals. 
Check the wiring. 

Fluid leaks to the outside of the valve when 
the ACTIVAL is in fully closed position. 

Actuator pointer not pointing to fully closed 
position 

Fully close the ACTIVAL. 

The valve vibrates or produces an 
abnormal noise. 

Primary pressure condition 
Differential pressure condition 

Adjust the mounting position and change the 
installation location. 

The auxiliary switch does not operate. 

Auxiliary switch (cam switch) condition 
Loosened terminals 
Wiring condition / disconnected wires 

Redo the cam switch setting. 
Tighten the terminals. 
Check the wiring. 

Valve hunting occurs. 

Secondary pressure condition 
Differential pressure condition 
Control stability 

Adjust the mounting position and change the 
installation location. 
Correct the control parameter setting of 
controller. 

Operating time of the spring return is too 
short. 

Wiring condition of the brake motor 

Consult with our sales/service personnel. 

Operating time of the spring return is too 
long. 
The spring return does not operate. 

Torque of valve operation 

Consult with our sales/service personnel. 

The actuator does not fully closes the valve 
(in 0 % position). 

 

Consult with our sales/service personnel. 

Input signal disagrees with the feedback 
output signal. 

To completely shut off the valve, valve open and close (0-100% position) operation is controlled 
by 10-90 % range of actuator voltage/current input signal. Input signal therefore disagrees with 
the feedback signal, and this is not an error. 

 

 

Содержание AB-7352-U

Страница 1: ...t water control and for steam control applicable to high differential pressure large Cv value high rangeability and low leakage Durable actuator with low power consumption Equal percentage flow charac...

Страница 2: ...e product might cause injury or product damage Detach the cover only when wiring setting the product or maintenance and reattach the cover after wiring setting the product or maintenance Failure to do...

Страница 3: ...the terminal screws might cause fire or overheating Do not touch the moving parts of the product Doing so might cause injury Dispose of this product as industrial waste in accordance with your local...

Страница 4: ...specifications Item Specification Model Two way valve with flanged end connection proportional control Body pressure rating ANSI Class125 equivalent Max working pressure 230 psig End connection ANSI...

Страница 5: ...Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition Limit operating condition Transport storage conditions packaged 2 Ambient tempe...

Страница 6: ...1 7 09 0 75 4 41 9 lb DN65 mm 314 124 190 90 20 140 180 19 19 kg VY5198K0081S 147 3 in 12 40 4 92 7 99 3 94 0 87 6 00 7 48 0 75 4 48 7 lb DN80 mm 315 125 203 100 22 152 4 190 19 22 1 kg Model VY5198H0...

Страница 7: ...AB 7352 U 7 Parts Identification Figure 2 Parts identification...

Страница 8: ...ication of the selector switches Figure 3 Selector switches Open close selector switch for input signal failure If no control signal is input the actuator automatically closes 0 or opens 100 the valve...

Страница 9: ...rrow indicated on the valve body Installation location CAUTION Do not install the product nearby a steam coil pressurized hot water coil or any high heat source High temperature radiation might cause...

Страница 10: ...position the valve and flush the pipes with the ACTIVAL installed at the maximum flow rate to remove all the foreign substances Factory preset position 0 For steam control drain retained water conden...

Страница 11: ...ept when connecting disconnecting wires Do not leave any refuse including metal chips after cutting a knockout hole and after connecting the wires inside the actuator Do not connect 24 V AC power to t...

Страница 12: ...terproof the wiring port For cable connection use a water proof connector Seal connector Part No 83104346 003 is recommended For conduit connection use a water proof plica tube or the like Terminals c...

Страница 13: ...transformer is required for ACTIVAL Transformer without isolation might damage the ACTIVAL and other devices connected to ACTIVAL Model SDC35 SDC36TC0 Model VY5198K VY5198H 4 to 20 mA DC input with 4...

Страница 14: ...Auxiliary switch Part No 83165274 001 Switches A and B actuating position Adjustable between 0 fully closed and 100 fully open Figure 11 Internal connection of Part No 83165274 001 OP1 OP2 OP3 N C N O...

Страница 15: ...es not operate at all Conditions of the power applied and of the input signal applied Loosened terminals Wiring condition disconnected wires Check the power supply and the controller connected to Tigh...

Страница 16: ...AB 7352 U Rev 4 0 Jun 2016 AB 7352 U 16 ACTIVAL is a trademark of Azbil Corporation in Japan or in other countries...

Отзывы: