ELECTRICAL SAFETY
1. Electrical equipment (including lines and plug connections) should not be defective.
2. The generating set must not be connected to other power sources, such as the power
company supply mains.
3. Protection against electrical shock depends on circuit breaker specially matched to
the generating set. If the circuit breakers require replacement they must be replaced
with a circuit breaker having identical ratings and performance characteristics.
4. Generating sets may only be loaded up to their rated power under the rated ambient
conditions. If generating set use is under conditions which do not conform to the
reference conditions as stipulated in this part of ISO 8528-8:2016, 7.1, if cooling of the
engine or alternator is impaired, e.g. as result of operation in restricted areas, and use
in higher temperatures, altitudes and humidity than those given in the reference
conditions, a reduction in power is necessary.
5. Due to high mechanical stresses only tough rubber-sheathed flexible cable(in
accordance with IEC 60245-4) or the equivalent should be used. When using extension
lines or mobile distribution networks the resistance value shall not exceed 1.5 Ω. For
reference, the total length of lines for a cross section of 1.5 mm² should not exceed
60 m; for a cross section of 2.5 mm², this should not exceed 100 m.
PRE-OPERATION CHECK
1. Filling the Engine Oil
SAE 10W-30 is recommended for general, all temperature use. Other viscosities shown
in the chart may be used when the average temperature in your area is within the
indicated range.
a) Remove the oil dipstick (7) and wipe the dipstick clean.
b) Check the oil level by inserting the dipstick into the filler neck without screwing it in,
c) Check the oil level. The oil level must between “H” and “L”. If near the lower level, fill
to upper level.
d) Tighten the oil dipstick (7).
CAUTION
!
Carefully pour in engine oil Avoid spilling!
2. Filling the fuel
You must fill the fuel before start the engine.
- Open the fuel tank cap.
- Fill in fuel to the fuel tank, do not higher than the warning line of the fuel tank.
- Close the fuel tank cap.
GB
81
|
82
GB