7- TROUBLESHOOTING 

Table 7.1 shows some comments about common reported problems. 

Table 7.1: Possible Errors and Solutions

 

NO  PROBLEM 

COMMENTS 

There is no output voltage 
in rescue operation 

 

Check MS (main switch) switch. It must be ON. 

 

Check if the batteries are connected correctly. 

 

Check 5V LED, it should be blinking. If not there may be a 
fault in electronic board. 

 

Check 15V LED, it should be ON. If not there may be a fault 
in electronic board. 

 

Check the BF (battery fuse). It must be present, not broken. 

There is no output voltage 
in normal operation 

 

Check LUP-NUP terminals. There should be an input voltage 
at 220V / 230V AC. 

Batteries are not charging 

 

Check the BF (battery fuse). It must be present not broken.  

 

Check that the batteries are connected correctly. 

5V led is always on 

 

Restart system and if led remain same, the electronic board 
may have a fault. 

5V led is always off 

 

Check If MS (main switch) switch is ON. 

 

Check if the batteries are connected correctly. 

 

If all are OK then the electronic board may have a fault. 

 

Содержание UPSLIFT

Страница 1: ...UPSLIFT EMERGENCY POWER SUPPLY FOR LIFTS USER MANUAL Version 1 2...

Страница 2: ...batteries It can be used in all kinds of controllers 2 Warning and Remarks Read user manual before starting to install the device Do not connect or disconnect any wire from terminals of the device whe...

Страница 3: ...imum 4 Ah See chapter 4 for selection Cutdown Battery Voltage 25V Max Input Current 30A Maximum Storage Temperature 70 oC Minimum Storage Temperature 20 oC Maximum Operating Temperature 70 oC Minimum...

Страница 4: ...3 2 Mechanical Dimensions mm Model H2 W d H1 UL180 210 180 125 170 Table 3 3 Mounting Dimensions mm Model d1 d2 d3 b1 b2 b3 a1 a2 UL180 106 190 53 10 30 18 37 13 9 Figure 3 1 Mechanical Dimensions Fi...

Страница 5: ...r then the current taken from the batteries by the motor should be taken into account for selecting the charge capacity of the batteries Table 3 2 shows the required wire cross sections and battery ca...

Страница 6: ...ments LUP Input Phase Terminal Line Voltage NUP Input Neutral Terminal PE Earth Connection LP Output Phase Terminal Emergency controller power supply outputs connected to the power supply input of the...

Страница 7: ...it which supplies energy to the peripherals is always active The device keeps the output voltage stable at 220V whatever the line condition is The device keeps the peripherals in the shaft unaffected...

Страница 8: ...be a fault in electronic board Check the BF battery fuse It must be present not broken 2 There is no output voltage in normal operation Check LUP NUP terminals There should be an input voltage at 220...