background image

UPSLIFT 

EMERGENCY POWER SUPPLY FOR LIFTS 

  

 

 

USER MANUAL  

Version: 1.2 

Содержание UPSLIFT

Страница 1: ...UPSLIFT EMERGENCY POWER SUPPLY FOR LIFTS USER MANUAL Version 1 2...

Страница 2: ...batteries It can be used in all kinds of controllers 2 Warning and Remarks Read user manual before starting to install the device Do not connect or disconnect any wire from terminals of the device whe...

Страница 3: ...imum 4 Ah See chapter 4 for selection Cutdown Battery Voltage 25V Max Input Current 30A Maximum Storage Temperature 70 oC Minimum Storage Temperature 20 oC Maximum Operating Temperature 70 oC Minimum...

Страница 4: ...3 2 Mechanical Dimensions mm Model H2 W d H1 UL180 210 180 125 170 Table 3 3 Mounting Dimensions mm Model d1 d2 d3 b1 b2 b3 a1 a2 UL180 106 190 53 10 30 18 37 13 9 Figure 3 1 Mechanical Dimensions Fi...

Страница 5: ...r then the current taken from the batteries by the motor should be taken into account for selecting the charge capacity of the batteries Table 3 2 shows the required wire cross sections and battery ca...

Страница 6: ...ments LUP Input Phase Terminal Line Voltage NUP Input Neutral Terminal PE Earth Connection LP Output Phase Terminal Emergency controller power supply outputs connected to the power supply input of the...

Страница 7: ...it which supplies energy to the peripherals is always active The device keeps the output voltage stable at 220V whatever the line condition is The device keeps the peripherals in the shaft unaffected...

Страница 8: ...be a fault in electronic board Check the BF battery fuse It must be present not broken 2 There is no output voltage in normal operation Check LUP NUP terminals There should be an input voltage at 220...

Отзывы: