AXOR Industries
Service Manual
Magnum400
TM
ver.2 rel.05/'15
The
magnum400
Tm
is made to be fixed vertically to the
bottom of the electrical box
in order to
guarantee reliable cooling, respecting the following distances:
2.2 Positioning
note
: Arrange the power components (converters, main's filters, resistors, terminals, ... ) in bins of
the electrical panel different from those reserved to the command or control systems (PLC, PC, CNC,
regulators, ...). This improves the level of immunity to interference of the system.
UP
MODE
DWN
SET
UP
MODE
DWN
SET
UP
MODE
DWN
SET
30
(1.18)
30
(1.18)
30
(1.18)
30
(1.18)
Ecc.
270
(10.62)
45
(1.77)
45
(1.77)
mm
INCHES
Cable duct
Cable duct
Conductive mounting panel
(zinc-coated)
The drive must be affixed
utilizing 2 or 4 socket
head screws DIN 912,
M5, paying attention that
the dissipating surface
and the mounting panel
maintain as much con-
tact as possible, in order
to guarantee maximum
thermal dissipation.