24
PROBLEM
POSSIBLE CAUSE
SOLUTION
Insufficient water
– Supply pressure inadequate
– Thermostatic cartridge filter dirty
– Showerhead screen washer or filter
gasket dirty
– Check water pressure (If a pump
has been installed check to see if
the pump is working).
– Clean filters
– Clean screen washer or filter gasket
Crossflow: hot water being forced
into cold water supply, or vice versa,
when mixer is closed
– Check valves dirty or worn
– Clean check valves,replace if
necessary
Output temperature does not cor-
respond with temperature set
– Handle not justified
– Justify the handle
Output temperature is erratic
– Temperature regulator dirty or
calcified
– Clean temperature thermostatic
cartridge filters
– Replace thermostatic cartridge
Output water is all hot or all cold
-- doesn't mix (new installation)
– Rough valve is cross connected --
hot on right and cold on left
– Remove function block, turn it 180°
and reinstall.
Safety stop override button not
operating
– Spring defective
– Button dirty
– Clean spring and/or button,
replace if necessary
T R O U B L E S H O O T I N G
MAINTENANCE
⁄ Inspect the check valves at least once per year.
Replace the check valves if necessary.
⁄ Should the volume of water decrease over time,
inspect and clean the filters on the thermostatic
cartridge. After reassembly, set the high temperature
limit stop and justify the handle.
⁄ To prolong the life of the themostatic cartridge, regu-
larly run it through its full range of temperatures.
Содержание Bouroullec 19702001
Страница 21: ...21 USER INSTRUCTIONS INSTRUCTIONS DE SERVICE MANEJO 104 F 104 F 1 2 ...
Страница 22: ...22 M A I N T E N A N C E E N T R E T I E N M A N T E N I M I E N T O 4 5 6 1 2 3 4 mm 24 mm 3 mm 4 mm ...
Страница 23: ...23 Go to page 12 Voir la page 12 Vease la página 12 24 mm 7 8 9 4 mm 4 mm 10 11 red rouge rojo ...
Страница 30: ...30 ...
Страница 31: ...31 ...