AXIS D2050-VE Network Radar Detector
Product overview
Mounting direction
The detector covers an angle of ±60° from its central axis. This means that if you mount it on a wall there is a blind spot to each
side of the detector.
To cover the wall you can move the radar module inside the detector.
1
-25° mounting direction
2
0° mounting direction
3
25° mounting direction
Mounting height
For optimal performance, install the detector 3.5 m (11 ft) above ground.
Note
If you install the detector at a different height, enter the actual mounting height in the product’s web pages before
calibrating the radar.
The following table shows the detection range at different mounting heights when detecting a 1.8 m (6 ft) tall person walking.
Mounting height
3.5 m (11 ft)
4 m (13 ft)
4.5 m (15 ft)
5 m (16 ft)
Near detection limit
4.5 m (15 ft)
6 m (20 ft)
7 m (23 ft)
8.5 m (28 ft)
Far detection limit
(max. values)
49 m (161 ft)
51 m (167 ft)
51 m (167 ft)
52 m (171 ft)
5