PESHEAT2V01
2016-01-08
22
Maximum rated value of pressure
sensors, kPa
(0,0…25000) kPa
The pressure value used in
calculations of heat *, kPa
(0,0…9999,9) kPa
If specify "0.0 kPa" - for calculation is
used the measured pressure value
(p1 – for flow pipe , p2–for return pire)
Thermal energy units *
MWh (kWh), Gcal ar GJ
Measurement units of quantity of a
liquid of 1-th flow measurement
channel
For choice:
m
3
or t
Measurement units of quantity of a
liquid of 2-nd flow measurement
channel
For choice:
m
3
or t
Report printing language and
communication with the printer
interface type
Report language: Prnt-P –Russian,
Prnt-L – Lithuanian, Prnt-E –English.
Communication with the printer interface
type:
1-wire interface, 2-optical interface
Parameter, derivable to 1
st
pulse
frequency output
MWh –thermal energy, m
3
- flow rate,
kW-thermal power,
o
C –temperature,
kPa-pressure, 1...4 -number of
measurement channel, 1-2 difference
Parameter, derivable to 2
nd
pulse
frequency output
MWh –thermal energy, m
3
- flow rate,
kW-thermal power,
o
C –temperature,
kPa-pressure, 1...4 -number of
measurement channel, 1-2 difference
Regulation function
and settings of regulable
(controlled) parameter
OFF – regulation function is disabled,
On1 or On2 – type of active operating
mode,
Regulable parameter:
kW-power,
o
C –
temperature, m
3
/h –flow rate, kPa-
pressure.
1…3 – number of channel.
Mode On1 -lower limit (the
minimum allowed value) for
regulated parameter.
Mode On2 - preset room
temperature
kW –power, m
3
/h-flow rate,
o
C –temperature, kPa –pressure.
1...4 - number of measurement channel.
1-2 –difference
Mode On1 - upper limit (the
maximum allowed value) for
regulated parameter
Mode On2 - adaptation
coefficient
kW –power, m
3
/h-flow rate,
o
C –temperature, kPa –pressure.
1...4 - number of measurement channel.
1-2 –difference
Valve runtime, s
0…999 s
Pause between actuation period
(actuation period is equivalent to
1% of the preset valves runtime, s
0…999 s