UMAX180800, 20 Thermocouple, 2 RTD, 4 Inputs, 6 Relays Dual CAN Controller
Version 1
Page: 64-71
To flash the new firmware, the user should click on
toolbar icon or from the
File
menu
select the
Open Flash File
command. The
Open Application Firmware Flash File
dialog will
appear. Pick up the flash file with the new converter firmware and confirm the selection by
pressing the
Open
button. The
Flash Application Firmware
dialog window will appear
1
, see
Figure 33. Flashing New Firmware. Preparation
1
In this example, instead of the new firmware, the old firmware V1.00 is being simply re-flashed.
Now the user can add any comments to the flashing operation in the
Flashing Comments
field.
They will be stored in the
Bootloader Information
group after flashing.
The user can also check the
Erase All ECU Flash Memory
flag to erase all inclinometer flash
memory. This operation, used in other products to reset configuration parameters kept in the
flash memory to their default values, has no effect on this product. This is because the
configuration parameters of the inclinometer are stored in a separate EEPROM memory.
Select the
Flash ECU
button to start flashing. A reminder that the old application firmware will
be destroyed by the flashing operation will appear. Press
Ok
to continue and watch the
dynamics of the flashing operation in the
Flashing Status
field. When flashing is done, the
following screen will appear prompting the user to reset the ECU, see Figure 34.