UMAX090690. Version: 1.2 Preliminary Documentation
– May Be Subject To Change
25-37
Name
Range
Default
Event Generates a DTC in DM1
False/True
1; True
Event Only Cleared by DM11
False/True
0; False
Lamp Set by Event in DM1
Drop List
0
SPN for Event used in DTC
0…524287
0
FMI for Event used in DTC
Drop List
0
Delay Before Sending DM1
0…60000
100
Table 21
– Default Diagnostic Input Setpoints
5.6.
CAN Receive Setpoints
The CAN Receive function block is defined in Section 4.6. Please refer to that section for detailed
information about how all these setpoints are used.
Screen Capture of CAN Receive Setpoints
Name
Range
Default
Signal Type
0…2
2
– Continuous
Is From Selected Address
True/False
1; True
Selected Address
0…255
0x00
Receive PGN
0…65535
65280 ($FF00)
Pos Byte
0-6
0; 1
st
Byte Position
Pos Bit
Drop List
N/A
Receive Data Size
Drop List
Continuous 2-Byte
Receive Data Resolution
-10
6
to 10
6
1
Receive Data Offset
-10
4
to 10
4
0
Receive Data Minimum
-
0xFFFFFFFF…DataMax 0
Receive Data Maximum
DataMin
…0xFFFFFFFF
100
Receive Message Timeout
0…60000
0 [ms]
Table 9
– Default CAN Receive Setpoints