Version 2.0.3 Preliminary Documentation – May be Subject to Change 8-36
For each output type, if the control signal is one of the inputs on the board, then there are up to six
output profiles that can be selected to determine how the output will react to a change at the input.
See the graphs below for a description of the profiles. See sections
4.2
and
4.5
for a description of
the profile setpoints.
WARNING: If the control input is set to a Digital type, the output will simply jump
to the maximum setpoint when the input is ON, and jump to the minimum
setpoint when the output is OFF.
NOTE: For outputs that are controlled using a J1939 Command Message, only the
"Single Profile" responses will be used (single or dual slope)
SINGLE PROFILE
Maximum
I [mA]
INPUT
0
Error Minimum
ER
RO
R M
O
DE
ER
RO
R M
O
DE
Breakpoint
Minimum
Minimum
Breakpoint Minimum
Maximum
Error Maximum
Single Slope
Dual Slope
Either, with Error Checking
Either, no Error Checking
Figure 1 – Analog Output Single Profile