Accessories and Additional Configuration Parameters 

SYSTEM ALARMS

 

 

 

 

 

 

 

 

Switches and timer delays 

Type 

Default Set point

 

Default Timer delay (sec) 

AXi international’s part number 

Vacuum switch 

16 in. hg 

5.0 

aa-0528 

Pressure switch 

22 psi 

0.0 

aa-0526 

Flow switch 

2.5 gpm 

10.0 

aa-0576 

 

Replacement Filter Elements  

Primary Filter/Water Separator:  

01060S - 60

μ

 Stainless Steel re-usable, cleanable filter element  

01030 - 30

μ

 replacement filter element  

01010 - 10

μ

 replacement filter element  

 

Fine Filter:  

WB-3 - 3

μ

Water Block Filter  

WB-10 - 10

μ

 Water Block Filter 

FFZ-3 - 3

μ

 Fine Filter  

FF-10 - 10

μ

 Fine Filter  

 

System Identification 

Serial Number: 

___________________________________________ (e.g. B090010-6003)  

 

Inspected By:

 ____________________________________________ 

Date:

____________ 

  

Содержание STS 6003

Страница 1: ...Dr Fort Myers FL 33905 239 690 9589 Toll Free 877 425 4239 FAX 239 690 1195 www AXI International com STS STS 6003 7003 Instruction Operating Maintenance Manual ENCLOSED FUEL MAINTENANCE SYSTEM REV03...

Страница 2: ...REV03016703010220 1...

Страница 3: ...rical 11 Field Connections If Applicable 11 Plumbing 11 Typical Plumbing Installation Schematically 12 Important Installation Precautions 12 Multi Tank Installation If Applicable 12 Controller 14 Sett...

Страница 4: ...tom Troubleshooting Guide 22 AXI International Limited Warranty 23 Warranty Claim Procedure 24 Technical Assistance and Ordering 25 Accessories and Additional Configuration Parameters 25 Replacement F...

Страница 5: ...C Operating Temperature 7000 Series 41 122 F 5 50 C Electrical 120V 60Hz 15A 1Ph or 230V 50Hz 15A 1Ph Pump 1 3 HP Spur Gear Pump Suction Capability Primed 15ft vertical lift or 100ft horizontal run li...

Страница 6: ...Water Detection Alarm Module Vacuum Pressure Switches Flow Switch Leak Detection Float Switch Inlet and Outlet Isolation Ball Valves Pump Motor 1 3 HP Gear Pump Primary Filter Water Separator Fuel Fil...

Страница 7: ...in Valve Basket Strainer Water Collection Drum o High Water Level Float Switch Manual Additive Injection If Applicable System Ball Valve Additive Injection Port Injection Port Ball Valve Auto Additive...

Страница 8: ...ion o Activated when the Vacuum Switch placed on the suction side of the pump set detects a reading above the factory set point The system will go into an alarm state and the pump will not be allowed...

Страница 9: ...or operate system without high fuel level alarms from both tanks tied into the control panel Frequently test overflow alarms for proper functionality and pump shutdown Auto Water Drain AWD If Applicab...

Страница 10: ...the treatment ratio For example 5 Gallon Jug of AFC treats 25 000 gallons of fuel so enter 1 5000 6 Once this information is entered press the START button to begin the injection process 7 There is a...

Страница 11: ...lectrical problems Immediately report or note any damages to the shipper Checklist If the packing crate shows signs of damage inspect the system for damage Check the entire system for damage that coul...

Страница 12: ...to the ground studs provided as shown on the provided drawings After the initial wiring of the system check operation to ensure that the motor is running in the correct direction If the motor is runn...

Страница 13: ...ed piping size Ref Page 4 Inlet Outlet Port or more with no additional flow restrictions That includes valves 90 degree connectors or other plumbing accessories For continuous optimal performance make...

Страница 14: ...vided electrical drawings must be wired to the Normally Closed High Level Alarm Contacts on both tanks to avoid overfilling of either tank and potential spills This is a very important safety feature...

Страница 15: ...the arrow key to select the Timer and Press OK 5 Use the arrow keys to select the desired field and press OK to edit 6 Use the left and right arrow keys to select the day days of the week the system...

Страница 16: ...IP Address 1 From the Main Menu press the CONFIG button 2 Input 9999 and press the enter key 3 Push IP Config and continue onto the next page 4 Enter the desired values for the PLC IP Address PLC IP...

Страница 17: ...m gauge on the input side of the pump The gauge should read no more than 15 HG vacuum maximum under normal conditions Vacuum gauge readings reaching 16 HG indicate excessive debris in the primary filt...

Страница 18: ...ssioning section Flow Switch When the flow rate drops below the predetermined set point on the flow switch i e 10 GPM the switch will trigger a signal to shut down the pump If the set point is incorre...

Страница 19: ...igh Pressure alarm should be indicated on the System Controller Open the outlet ball valve again Reset the alarm by pushing the Alarm Reset button on the enclosure door panel Water Sensor Jump the Wat...

Страница 20: ...hs Servicing the Primary Filter Water Separator Clogged primary filter elements restrict the flow of fuel resulting in the system s vacuum gauge indicating a pressure drop The gauge reads the conditio...

Страница 21: ...rn the enclosure door panel selector switch to its original position 9 Check for leaks when re starting and pressurizing the system Note Disposal of fuel associated waste and filters must be in accord...

Страница 22: ...icing of Water Separator 1 Keep a fuel waste container under the Manual Drain Port 2 Open the bleed screw on top of the Water Separator to break vacuum 3 Open the AWD Isolation Ball Valve and Manual D...

Страница 23: ...ve water in tank 2 Restriction in plumbing on discharge side too high 3 Head on discharge side too high 4 Check valve stuck or defective 5 Outlet ball valve not fully open 6 Discharge line clogged Pum...

Страница 24: ...t limited to improper installation or location in a harsh corrosive or saltwater environment 5 Failures resulting from attachments accessory items and parts not sold by AXI International 6 Repairs by...

Страница 25: ...purchase model number serial number and a detailed explanation of the problem you are experiencing The Customer Service Representative may at the discretion of AXI International arrange for a Field E...

Страница 26: ...eters SYSTEM ALARMS Switches and timer delays Type Default Set point Default Timer delay sec AXi international s part number Vacuumswitch 16 in hg 5 0 aa 0528 Pressure switch 22 psi 0 0 aa 0526 Flowsw...

Отзывы: