Safety Instructions Part A
The device contains fuses that are under electrical voltage. Danger to life by electric shock. Replace
the fuses only in a non-energized state. Observe electrical safety regulations.
Leakages in the AwiCONTAINER may create a hazardous atmosphere. The ventilation grilles are
important in order to dilute the air in case of leakages. These must not be closed.
Carbon monoxide is odorless and toxic. It can accumulate in the AwiCONTAINER. A poisoning can
be deadly. With carbon monoxide-containing gas, install a suitable CO gas alarm sensor.
Leaking fuel gas mixture may cause an explosion hazard in the AwiCONTAINER. Install an
electrocatalytic gas warning sensor, except for biogas with low leakage flow (pressure at sampling
point max 20 mbar) or low flammable gas concentration (less than 4 % v/v).
Gas warning sensors can deliver too low readings or even become unusable due to hydrogen
sulphide in the air. Calibrate gas warning sensors in according to manufacturer's recommendation
(every 6 months). If the ambient air contains hydrogen sulphide, shorten the calibration interval (to 3
months).
The gas analysis system contains icons with the following meaning:
Attention, General Hazard Point. Refer to the documentation. Disregarding this can
lead to death or serious personal injuries or property damages.
Warning of dangerous electrical voltage.
Please also observe the safety instructions in Part B!