Avtron HS6A Скачать руководство пользователя страница 2

HS6A

2

The hollow shaft HS6A design eliminates the potential for coupling 

failures from misalignment, however, excessive housing movement 

(wobble) may cause undesirable vibrations and bearing damage. The 

higher the RPM, the more severe the vibration will be from housing 

movement. In a typical installation a housing movement of 0.007” 

[0.18mm] TIR or less (as measured at the outside diameter of the 

main encoder body) will not have an adverse effect.

1)  Disconnect power from equipment and encoder cable.

2)  Use caliper gauge to verify motor shaft is proper diameter and  

 

within allowable tolerances: +0.000”, -0.0005” 

 

[+0.00, -0.013mm].

3)  Clean machine shaft of any dirt and remove any burrs.

4)  Use dial indicator gauge to verify the motor shaft: Total  

 

 

Indicated Runout (TIR) <0.002” [0.05mm].

5)  Install the anti-rotation bracket tether to the face of the encoder  

 

using screws and lock washers, included with the tether. 

6)  Loosen clamping collar screw.

7)  Test Fitting: carefully slide the encoder onto the shaft to verify    

 

fit. Ensure a minimum of 1/8” [2mm] between encoder and  

 

mounting surface. DO NOT FORCE. Encoder should slide on  

 

easily. If the encoder does not fit easily, remove it, verify shaft  

 

size, and check for burrs and shaft damage.

8)  Slide the HS6A at least 1” [25mm] onto the shaft.   

9)  Tighten screws on clamping collar.

 

DO NOT USE A STANDARD RIGHT ANGLE WRENCH. Use only a  

 

T-handle hex wrench or torque wrench with hex bit.

10)  Secure free end of the anti-rotation tether to frame using bolt  

 

or T-bolt. The bracket should be parallel to the encoder  

 

face, 90 degrees to the shaft to avoid encoder bearing damage.   

 

Use additional washers as needed to ensure the tether is  

 

parallel to the encoder face.

11)  Turn shaft by hand and verify the shaft turns freely and does  

 

not produce excessive runout/wobble of the encoder (<0.007”  

 

TIR [0.18mm], Total Indicated Runout.)  Ensure the tether is  

 

secure and the encoder body cannot rotate.

12)  Connect cable as shown in wiring diagram.

13)  Apply power to the encoder.

14)  Rotate the shaft by hand, or using jog mode of the speed  

 

controller and verify proper direction and position output.

 

ENVIRONMENTAL CONSIDERATIONS

Follow these steps to reduce potential problems:

1)  Always mount connection points, conduit couplings, junction  

 

boxes, etc., lower than actual encoder.

2)  For washdown areas, shroud or otherwise cover the encoder to  

 

prevent direct water spray. Do not attach the shroud directly to  

 

the encoder.

 

REPAIRS

 

REMOVAL INSTRUCTIONS:

1.  Unbolt tether from mounting point on motor or machine.

2.  Loosen clamping collar screw.

3.  Slide the encoder off the shaft.

REPLACING PARTS

 

The HS6A has two items that are user-replacable in the field in case 

of damage:

1.   Shaft sizing insert: Simply slide the insert out of the HS6A and   

 

replace it with the new bore size insert.  Insert should remove  

 

and install with modest force-do not pound the insert into the  

 HS6A.

2.   Tether system:  To replace the tether system, remove the  

 

retaining screw(s), then replace with the new tether.

 

CAUTION

 

Do not attempt to remove, service, or adjust any of the  

 

internal components of the HS6A.

WIRING INSTRUCTIONS

 

 

CAUTION

 

Remove power before wiring.

 

Interconnecting cables specified in the wire selection chart are 

based on typical applications. Refer to the system drawing for 

specific cable requirements where applicable.

Physical properties of cable such as abrasion, temperature, tensile 

strength, solvents, etc., are dictated by the specific application and 

communications bus. Do not use unshielded cable.  Ground one end 

(only) of the shield to earth ground.

Do not run encoder wiring parallel to power cable wiring for 

extended distances, and do not wrap encoder cable around power 

cables.

TROUBLESHOOTING:

If the controller indicates a loss of encoder fault, check the encoder 

power supply at the encoder. If power is present at the encoder, 

check polarity. If the wiring appears correct and in good shape, 

test the wiring by replacing the AV6M. If the controller still shows 

encoder loss/fault, then the wiring is faulty and should be repaired or 

replaced.

An oscilloscope can also be used to verify output of the HS6A 

encoder at the encoder connector itself and at the drive/ controller 

cabinet.  Depending on the communication method, signals will vary 

but the oscilliscope should show the output signals varying.  Keep in 

mind that SSI and Profibus DP are master-slave systems and require 

the controller to  signal the encoder to transmit position.

Read each section for specifics about each bus and troubleshooting 

tips.

SSI TROUBLESHOOTING

For SSI, monitor the clock input line to ensure the controller is 

triggering the encoder to send position.  The clock should obey the 

signal requirements shown in the SSI signal section, and should 

appear as a rapid set of transitions on the clock line.  The encoder 

data transmit lines should change state as data is clocked out.  Note 

that the varying binary patterns representating position can produce 

pulses of varying width--this is normal.

PROFIBUS-DP TROUBLESHOOTING

Viewing on oscilliscope:  for Profibus DP, the transmit and receive 

signal pairs should change state rapidly as the controller transmits 

messages to the encoder and the encoder replies.  Transmission 

rates vary, but these messages can be extremely short and typically 

require scope triggering to spot them.  

For Profibus DP, ensure termination resistors are in place (or 

switched on) at each end of the cabling system, and that no 

termination resistors are in placed or activated in the middle of 

the system.  Remove the connections to the master controller and 

all devices, or power down all devices.  Measure the resistance 

between the communication wires. The value should be ~1/2 of the 

termination resistor value on the network. If the resistance is greater 

than the limit, a termination resistor is missing from the network. If 

the resistance is less than the limit, there are incorrect termination 

resistors switched on or connected to the system.

CANOPEN TROUBLESHOOTING

For CANOpen: disconnect the power connection, then ensure there 

are no short circuits between any of the signal or power wires or 

shield.

Viewing on oscilliscope: for CANOpen the transmit and receive 

signal pairs should change state rapidly as the controller transmits 

messages to the encoder and the encoder replies.  Transmission 

rates vary, but these messages can be extremely short and typically 

require scope triggering to spot them.  

Содержание HS6A

Страница 1: ...tion into a safety system CAUTION Be careful not to damage clamping fingers of hollow shaft during handling Do not tighten clamping collar before installation onto motor shaft WARNING Installation should be performed only by qualified personnel Safety precautions must be taken to ensure machinery cannot rotate and all sources of power are removed during installation INSTALLATION Refer to the back ...

Страница 2: ...emove power before wiring Interconnecting cables specified in the wire selection chart are based on typical applications Refer to the system drawing for specific cable requirements where applicable Physical properties of cable such as abrasion temperature tensile strength solvents etc are dictated by the specific application and communications bus Do not use unshielded cable Ground one end only of...

Страница 3: ...s PCAN View Ensure the device is set to the proper baud rate connection cap or for units with no connection cap via software Ensure the device is set to the proper node address connection cap or for units with no connection cap via software The encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 If you cannot see this message try power cycling the device N...

Страница 4: ...Line Driver Specs See table G Connectors See connector options on page 1 H Accuracy 0 04 deg 2 6 arc min 12 bit units 0 02 deg 1 3 arc min 16 bit units MECHANICAL A Shaft Inertia 0 00003lb in sec2 30 g cm2 dyn B Acceleration 6000 RPM Sec Max C Speed 6000 RPM Max EOS model std seals 3000 RPM Max 12mm thru shaft model 12000 RPM Max w o seals not recommended D Weight 1 2 2 7 lbs 550 1200g E Vibration...

Страница 5: ... encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 nn node number typically 0x01 for units with connection cap including hardware node and baud rate selection software commands will not change node 0x20 is the factory default for units with software selectable addressing software commands can change node number Setting Node Number To set the node number ...

Страница 6: ...x620 0x22 0x00 0x23 0x00 0x55 0xAA 0xAA 0x55 No reset is triggered Cycle power after saving changes to parameters Other Parameters Contact Nidec Avtron for additional parameters diagnostic registers cam and programmable limit switch functionality and other advanced features CANOPEN TROUBLESHOOTING For CANOpen disconnect the power connection then ensure there are no short circuits between any of th...

Страница 7: ... cycled before the values are stored the encoder will default to the values previously stored in EEPROM Setting Node Number To set the node number on units with a connection cap Set the address using the two rotating switches The node number can be between 0 63 The node address X10 switch 10 X1 switch value To set the node MAC ID number on units without a connection cap write attribute 6Fh byte ma...

Страница 8: ... cabling system and that no termination resistors are in placed or activated in the middle of the system Remove the connections to the master controller and all devices or power down all devices Measure the resistance between the communication wires Example DeviceNet measure between CAN_L and CAN_H The value should be 1 2 of the termination resistor value on the network For DeviceNet this value sh...

Страница 9: ...ian lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided directly above the single turn data bitwise Example 12 turns x 13 bits turn encoder lowest 13 bits position within one turn next 12 bits up to bit 25 represent turns position data The position data is provided at parameter 0x6004 Setting Zero Position for Multiturn...

Страница 10: ...ors encoder operational LS DA 1 Status Flashing Green Active inbound communication LS DA 2 Status Green Output connected to next encoder LS DA 2 Flashing Green Active communication to next encoder Error Red Ethernet Error or invalid node address Status 1 Flash Pre Operational Mode 1 2 Flashes Pre Operational Mode 2 3 Flashes Ready to operate Blinking Stopped ...

Страница 11: ... position data Setting Zero Position for Multiturn Encoders and Single turn Encoders NOTE Do not attempt to use zero preset function while the encoder is rotating Doing so will produce unpredictable results To set zero position raise the voltage level of the Preset input to V supply of the encoder for at least 0 1sec The encoder will set the outputs to zero Setting Direction of Rotation for Count ...

Страница 12: ...ition Speed and Acceleration To read position into your device acceleration and speed measurement is not supported For multiturn single turn encoders position data provided as 4 bytes 32 bits Format is little endian lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided in adjacent 32 bit words Example 12 turns x 13 bits t...

Страница 13: ...ted to each cable Use hubs or switches to connect multiple Modbus TCP encoders to the master device A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Initial Value parameter may have been loaded into the encoder at the wrong physical position of the machine Drive the machine to t...

Страница 14: ...now operate at the assigned IP address which can be validated using the ping command from the PC The assigned name can be used throughout STEP7 software to address the encoder Note that if more than one encoder is to be used on the same Profinet IO network each encoder must be assigned a unique name and individual encoders must be connected one by one to assign names using STEP7 software during se...

Страница 15: ...ncoder use the parameters supplied in the GSDML file to set the appropriate mode Store the resulting configuration into the scanner module Storing Saving Encoder Parameters to EEPROM To store the current encoder operating parameters into non volatile memory Other Parameters Contact Nidec Avtron for additional parameters diagnostic registers cam and programmable limit switch functionality and other...

Страница 16: ...placed in registers identified in the configuration package Profibus DP Diagnostic LEDs LED Status Meaning STATUS ERROR Green Off Power Ok Status OK STATUS ERROR Green Red No Configuration Data Received STATUS ERROR Green Flashing Red Encoder Bus Address Set Incorrectly STATUS ERROR Flashing Green Red Parameters Received With Incorrect Length STATUS ERROR Flashing Green Off Commissioning Mode Acti...

Страница 17: ...is required Measuring Position Speed and Acceleration To read position and speed into your device acceleration measurement is not supported Following the instructions for your master scanner module for the EtherNet IP network load the encoder EDS file into your configuration Assign it to the correct IP address node number Store the configuration to the scanner module All of the position data and o...

Страница 18: ...munication A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Preset parameter may have been loaded into the encoder at the wrong physical position of the machine Drive the machine to the home preset position and cycle power to see if the position is correctly reloaded EtherNet IP...

Страница 19: ...d Upon the Set Zero signal returning to logic zero falling edge the encoder count value will be set to zero Set Direction input 10K resistance For input logic zero or no connection the encoder will count UP for CCW rotation as viewed from the rear end of the encoder For input logic 1 10V Vs the encoder will count DOWN for CCW rotation as viewed from the rear of the encoder SSI TROUBLESHOOTING For ...

Страница 20: ...ost L GND 0V BROWN 3 NC PINK NC BLUE NC GRAY CAN_H Rightmost H CAN_L Rightmost L CAN_GND Rightmost G Double up Double up REF SIGNAL CAN_GND V CAN_H CAN_L GND 0V Optional Daisy Chain CAN_H CAN_L CAN_GND V GND 0V CANOpen Bus C HS6A WIRING DIAGRAMS NOTE CAN cable required with individual and overall shields Obey pairing as shown Term Strip Switches Pinouts Bus in Bus out ...

Страница 21: ...eftmost H CAN_L BLUE 3 Leftmost L NC NC NC CAN_H Rightmost H CAN_L Rightmost L Double up Double up REF SIGNAL V V GND CAN_H CAN_L Optional Daisy Chain CAN_H CAN_L GND V DeviceNet Bus D HS6A WIRING DIAGRAMS NOTE CAN cable required with individual and overall shields Obey pairing as shown Switches Pinouts Term Strip Bus in Bus out ...

Страница 22: ...bey pairing as shown optional overall shield may be used for high noise environments NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a Straight through connection Tx Tx Rx Rx Rx Rx Communication Bus K N R POWERLINK Profinet IO EtherNet IP Pinout Pinouts for Ethernet Port 2 Port 1 Power Switches HS6A WIRING DIAGRAMS Master Scanner o...

Страница 23: ... YELLOW BROWN 16 BIT 15 WHITE YELLOW 15 BIT 14 BROWN GREEN 14 BIT 13 WHITE GREEN 13 BIT 12 BLUE RED 12 BIT 11 GREY PINK 11 BIT 10 VIOLET 10 BIT 9 BLACK 9 BIT 8 RED 8 BIT 7 BLUE 7 BIT 6 PINK 6 BIT 5 GREY 5 BIT 4 YELLOW 4 BIT 3 GREEN 3 BIT 2 BROWN 2 BIT 1 LSB WHITE 1 NOTE Cable with overall shield required Communication Bus P Parallel Pinout REF SIGNAL SIGNAL GND Vs DIRECTION LATCH PRESET BIT 25 MSB...

Страница 24: ...hown optional overall shield may be used for high noise environments Communication Bus M Modbus TCP Pinout HS6A WIRING DIAGRAMS Master Scanner or Switch Power Supply NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a Straight through connection Tx Tx Rx Rx Rx Rx 1 4 2 3 5 2 3 1 4 Pinouts for Ethernet Port 1 Power ...

Страница 25: ... B Bus A out 5 pin female 2 Rightmost A Bus B out 4 Rightmost B REF SIGNAL GND OV Vs Bus A out Bus B out Bus A in Bus B in NOTE Profibus cabling required Obey pairing as shown If termination resistor R is enabled on bus out terminals are disabled Communication Bus P Profibus Pinout HS6A WIRING DIAGRAMS Power Supply Bus In Bus Out Pinouts for Profibus Power Bus out Bus in ...

Страница 26: ...INK 4 6 SET ZERO BLUE 9 7 SET DIRECTION RED 8 8 NC 5 NC 6 NC 7 NC 10 REF SIGNAL GND Vs CLK CLK DAT DAT SET ZERO SET DIRECTION NC NC NC NC NOTE Twisted pair cable required with overall shield individual pair shielding recommended Obey pairing as shown Communication Bus S SSI Pinout HS6A WIRING DIAGRAMS Pinouts for SSI Option F M23 12 Option E M12 8 ...

Страница 27: ...HS6A 27 HS6A SSI S 12mm Bore P End Thru Shaft Universal Mounting U Connector M12 8 E ...

Страница 28: ...HS6A 28 HS6A SSI S 15mm Bore R End of Shaft Mounting E Connector M23 12 F ...

Страница 29: ...2 1230 FAX 1 216 642 6037 www avtronencoders com HS6A Profibus DP P 15mm Bore R End of Shaft Mounting E Connector M12x3 C DIMENSIONS IN INCHES MILLIMETERS ALL DIMENSIONS ARE APPROXIMATE Features and specifications subject to change without notice Avtron standard warranty applies All dimensions are in millimeters approx ...

Отзывы: