HS6A 16

Profibus DP Protocol “P” 

Profibus DP is typically a master-slave network-the master/scanner 

device gathers data from each (slave) device on the bus.  Avtron 

encoders are Profibus DP slave devices. 

Profibus may be wired in several different configurations, but the 

most common is a “Daisy-Chain” configuration.  The master/scanner 

device may be located at any point along the bus.  The cable must 

be terminated at each end with 150 ohm resistors.  These resistors 

can be present in the D-sub cable connectors, in the master 

controller, and in the encoder, but only one at each end of the bus, 

two total should be connected/enabled.  Note that Profibus DP also 

offers the option to carry device power to each encoder through an 

additional cable pair of wires.  

Preferred cable:  Nidec Avtron recommends structured Profibus DP 

wiring systems, available from a broad range of vendors.  

For more details on Profibus, consult the Profibus Users Association 

(PI):

http://www.profibus.com/

Number 

of 

Nodes

2

16

32

64

Units

Max. 

Overall 

Cable 

Length*

750

[229]

690

[210]

640

[190]

560

[170]

ft 

[m]

Network 

Baud 

Rate

12M 

6M 

3M

1.5M

500K 187.5K 93.75K 

45.45K 

19.2K 

9.6K

Units

Max. 

Length*

325

[100]

650

[200]

1300

[400]

3250

[1000]

4000 

[1200]

ft 

[m]

*Using Profibus standard cable, 150 ohm impedance 3-20mHz, 
<30pf/m, <110 ohms/km loop resistance

Setting Station/Node, Baud Rate & Termination Resistor

To set the node number: use the rotating switches in the connection 

cap.  The format is decimal, from 0-99 (ten’s switch and one’s 

switch).  Software/master address changes are not supported. 

NOTE:  Each device must have a unique node address, and this 

address must be different than the master/scanner module. 

Profibus DP baud rate is auto-detected by the encoder, no settings 

are required. 12 MBaud, 6 MBaud, 3 MBaud, 1.5 MBaud, 500 kBaud, 

187.5 kBaud, 93.75 kBaud, 45.45 kBaud, 19.2 kBaud, 9.6 kBaud are 

all supported.

To enable the termination resistor:  Move the switch “R” to the “On” 

Position on the connection board.  The termination resistor should 

be turned on/enabled when the encoder is the last/only device on 

the bus.  Note that standard 9 pin DIN connectors used for Profibus 

DP also offer a termination resistor.  Be sure NOT to enable both the 

encoder termination resistor and the 9-pin connector resistor, use 

one or the other for an encoder at the end of a bus.

Measuring Position, Speed, and Acceleration

To read position and speed feedback into your device (Acceleration 

measurement is not supported directly):  Following the instructions 

for your master/scanner module for the Profibus DP network, load 

the encoder GSD file into your configuration.  Assign it to the correct 

node number.  Store the configuration to the scanner module.  

All of the position data and other parameters will be read by 

the scanner module and placed in registers identified in the 

configuration package.

Profibus DP Diagnostic LEDs
LED

Status

Meaning

STATUS

ERROR

Green

Off

Power Ok, Status OK

STATUS

ERROR

Green

Red

No Configuration Data Received

STATUS

ERROR

Green

Flashing Red

Encoder Bus Address Set 

Incorrectly

STATUS

ERROR

Flashing Green

Red

Parameters Received With 

Incorrect Length

STATUS

ERROR

Flashing Green

Off

Commissioning Mode Active

STATUS

ERROR

Off

Red

No Data Received, Bus Inactive

STATUS

ERROR

Off

Off

No Power

For multiturn & single turn encoders:  position data provided as 

4 bytes, 32 bits:  Format is little-endian (lowest bit = right-most 

bit).  Single-turn data/data within 1 turn is provided in the least-

significant bits.  Multiturn data is provided directly “above” the 

single turn data, bitwise.  Example:  12 turns x 13 bits/turn encoder, 

lowest 13 bits = position within one turn, next 12 bits (up to bit 25) 

represent turns position data.

Setting Zero Position for Multiturn Encoders and Single turn 

Encoders Using 32 Bit Feedback:

Write 1 to the highest bit (31)-write 128 (80H) to top-most-byte of 

the position register.

For single turn encoders:  position data can instead be provided as 2 

bytes, 16 bits:  Format is little-endian (lowest bit = right-most bit).  

Setting Zero Position for Single turn Encoders Using 16 Bit 

Feedback :

Write 1 to the highest bit (15)-write 128 (80H) to top-most-byte of 

the position register.

Isochronous (Auto-Transmit) Mode

DPV2 Isochronous communication can be configured using the 

optional DPV2 GSD file.  Load the encoder GSD file into your master/

scanner software.  Assign it to the correct node number.  Store the 

resulting configuration into the scanner module.  Note many Profibus 

master devices do not support isochronous mode-check the master 

device manual before utilizing this encoder mode and GSD file.

Other Parameters

Contact Nidec Avtron for additional parameters, diagnostic registers, 

cam and programmable limit switch functionality and other 

advanced features.

PROFIBUS-DP TROUBLESHOOTING

Viewing on oscilliscope:  for Profibus DP, the transmit and receive 

signal pairs should change state rapidly as the controller transmits 

messages to the encoder and the encoder replies.  Transmission 

rates vary, but these messages can be extremely short and typically 

require scope triggering to spot them.  

For Profibus DP, ensure termination resistors are in place (or 

switched on) at each end of the cabling system, and that no 

termination resistors are in placed or activated in the middle of 

the system.  Remove the connections to the master controller and 

all devices, or power down all devices.  Measure the resistance 

between the communication wires. The value should be ~1/2 

of the termination resistor value on the network (typically = 75 

ohm measurement). If the resistance is greater than the limit, a 

termination resistor is missing from the network. If the resistance is 

less than the limit, there are incorrect termination resistors switched 

on or connected to the system.

Содержание HS6A

Страница 1: ...tion into a safety system CAUTION Be careful not to damage clamping fingers of hollow shaft during handling Do not tighten clamping collar before installation onto motor shaft WARNING Installation should be performed only by qualified personnel Safety precautions must be taken to ensure machinery cannot rotate and all sources of power are removed during installation INSTALLATION Refer to the back ...

Страница 2: ...emove power before wiring Interconnecting cables specified in the wire selection chart are based on typical applications Refer to the system drawing for specific cable requirements where applicable Physical properties of cable such as abrasion temperature tensile strength solvents etc are dictated by the specific application and communications bus Do not use unshielded cable Ground one end only of...

Страница 3: ...s PCAN View Ensure the device is set to the proper baud rate connection cap or for units with no connection cap via software Ensure the device is set to the proper node address connection cap or for units with no connection cap via software The encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 If you cannot see this message try power cycling the device N...

Страница 4: ...Line Driver Specs See table G Connectors See connector options on page 1 H Accuracy 0 04 deg 2 6 arc min 12 bit units 0 02 deg 1 3 arc min 16 bit units MECHANICAL A Shaft Inertia 0 00003lb in sec2 30 g cm2 dyn B Acceleration 6000 RPM Sec Max C Speed 6000 RPM Max EOS model std seals 3000 RPM Max 12mm thru shaft model 12000 RPM Max w o seals not recommended D Weight 1 2 2 7 lbs 550 1200g E Vibration...

Страница 5: ... encoder will power up in the pre operational mode The message it will issue is ID 0x07nn 0x00 nn node number typically 0x01 for units with connection cap including hardware node and baud rate selection software commands will not change node 0x20 is the factory default for units with software selectable addressing software commands can change node number Setting Node Number To set the node number ...

Страница 6: ...x620 0x22 0x00 0x23 0x00 0x55 0xAA 0xAA 0x55 No reset is triggered Cycle power after saving changes to parameters Other Parameters Contact Nidec Avtron for additional parameters diagnostic registers cam and programmable limit switch functionality and other advanced features CANOPEN TROUBLESHOOTING For CANOpen disconnect the power connection then ensure there are no short circuits between any of th...

Страница 7: ... cycled before the values are stored the encoder will default to the values previously stored in EEPROM Setting Node Number To set the node number on units with a connection cap Set the address using the two rotating switches The node number can be between 0 63 The node address X10 switch 10 X1 switch value To set the node MAC ID number on units without a connection cap write attribute 6Fh byte ma...

Страница 8: ... cabling system and that no termination resistors are in placed or activated in the middle of the system Remove the connections to the master controller and all devices or power down all devices Measure the resistance between the communication wires Example DeviceNet measure between CAN_L and CAN_H The value should be 1 2 of the termination resistor value on the network For DeviceNet this value sh...

Страница 9: ...ian lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided directly above the single turn data bitwise Example 12 turns x 13 bits turn encoder lowest 13 bits position within one turn next 12 bits up to bit 25 represent turns position data The position data is provided at parameter 0x6004 Setting Zero Position for Multiturn...

Страница 10: ...ors encoder operational LS DA 1 Status Flashing Green Active inbound communication LS DA 2 Status Green Output connected to next encoder LS DA 2 Flashing Green Active communication to next encoder Error Red Ethernet Error or invalid node address Status 1 Flash Pre Operational Mode 1 2 Flashes Pre Operational Mode 2 3 Flashes Ready to operate Blinking Stopped ...

Страница 11: ... position data Setting Zero Position for Multiturn Encoders and Single turn Encoders NOTE Do not attempt to use zero preset function while the encoder is rotating Doing so will produce unpredictable results To set zero position raise the voltage level of the Preset input to V supply of the encoder for at least 0 1sec The encoder will set the outputs to zero Setting Direction of Rotation for Count ...

Страница 12: ...ition Speed and Acceleration To read position into your device acceleration and speed measurement is not supported For multiturn single turn encoders position data provided as 4 bytes 32 bits Format is little endian lowest bit right most bit Single turn data data within 1 turn is provided in the least significant bits Multiturn data is provided in adjacent 32 bit words Example 12 turns x 13 bits t...

Страница 13: ...ted to each cable Use hubs or switches to connect multiple Modbus TCP encoders to the master device A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Initial Value parameter may have been loaded into the encoder at the wrong physical position of the machine Drive the machine to t...

Страница 14: ...now operate at the assigned IP address which can be validated using the ping command from the PC The assigned name can be used throughout STEP7 software to address the encoder Note that if more than one encoder is to be used on the same Profinet IO network each encoder must be assigned a unique name and individual encoders must be connected one by one to assign names using STEP7 software during se...

Страница 15: ...ncoder use the parameters supplied in the GSDML file to set the appropriate mode Store the resulting configuration into the scanner module Storing Saving Encoder Parameters to EEPROM To store the current encoder operating parameters into non volatile memory Other Parameters Contact Nidec Avtron for additional parameters diagnostic registers cam and programmable limit switch functionality and other...

Страница 16: ...placed in registers identified in the configuration package Profibus DP Diagnostic LEDs LED Status Meaning STATUS ERROR Green Off Power Ok Status OK STATUS ERROR Green Red No Configuration Data Received STATUS ERROR Green Flashing Red Encoder Bus Address Set Incorrectly STATUS ERROR Flashing Green Red Parameters Received With Incorrect Length STATUS ERROR Flashing Green Off Commissioning Mode Acti...

Страница 17: ...is required Measuring Position Speed and Acceleration To read position and speed into your device acceleration measurement is not supported Following the instructions for your master scanner module for the EtherNet IP network load the encoder EDS file into your configuration Assign it to the correct IP address node number Store the configuration to the scanner module All of the position data and o...

Страница 18: ...munication A software snoop or sniffer program can also be used to packet analyze the communication If the position is changing as the encoder moves but is reported incorrectly the Preset parameter may have been loaded into the encoder at the wrong physical position of the machine Drive the machine to the home preset position and cycle power to see if the position is correctly reloaded EtherNet IP...

Страница 19: ...d Upon the Set Zero signal returning to logic zero falling edge the encoder count value will be set to zero Set Direction input 10K resistance For input logic zero or no connection the encoder will count UP for CCW rotation as viewed from the rear end of the encoder For input logic 1 10V Vs the encoder will count DOWN for CCW rotation as viewed from the rear of the encoder SSI TROUBLESHOOTING For ...

Страница 20: ...ost L GND 0V BROWN 3 NC PINK NC BLUE NC GRAY CAN_H Rightmost H CAN_L Rightmost L CAN_GND Rightmost G Double up Double up REF SIGNAL CAN_GND V CAN_H CAN_L GND 0V Optional Daisy Chain CAN_H CAN_L CAN_GND V GND 0V CANOpen Bus C HS6A WIRING DIAGRAMS NOTE CAN cable required with individual and overall shields Obey pairing as shown Term Strip Switches Pinouts Bus in Bus out ...

Страница 21: ...eftmost H CAN_L BLUE 3 Leftmost L NC NC NC CAN_H Rightmost H CAN_L Rightmost L Double up Double up REF SIGNAL V V GND CAN_H CAN_L Optional Daisy Chain CAN_H CAN_L GND V DeviceNet Bus D HS6A WIRING DIAGRAMS NOTE CAN cable required with individual and overall shields Obey pairing as shown Switches Pinouts Term Strip Bus in Bus out ...

Страница 22: ...bey pairing as shown optional overall shield may be used for high noise environments NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a Straight through connection Tx Tx Rx Rx Rx Rx Communication Bus K N R POWERLINK Profinet IO EtherNet IP Pinout Pinouts for Ethernet Port 2 Port 1 Power Switches HS6A WIRING DIAGRAMS Master Scanner o...

Страница 23: ... YELLOW BROWN 16 BIT 15 WHITE YELLOW 15 BIT 14 BROWN GREEN 14 BIT 13 WHITE GREEN 13 BIT 12 BLUE RED 12 BIT 11 GREY PINK 11 BIT 10 VIOLET 10 BIT 9 BLACK 9 BIT 8 RED 8 BIT 7 BLUE 7 BIT 6 PINK 6 BIT 5 GREY 5 BIT 4 YELLOW 4 BIT 3 GREEN 3 BIT 2 BROWN 2 BIT 1 LSB WHITE 1 NOTE Cable with overall shield required Communication Bus P Parallel Pinout REF SIGNAL SIGNAL GND Vs DIRECTION LATCH PRESET BIT 25 MSB...

Страница 24: ...hown optional overall shield may be used for high noise environments Communication Bus M Modbus TCP Pinout HS6A WIRING DIAGRAMS Master Scanner or Switch Power Supply NOTE For encoder switch connections use the crossover pinout shown for encoder PC or encoder PLC direct wiring use a Straight through connection Tx Tx Rx Rx Rx Rx 1 4 2 3 5 2 3 1 4 Pinouts for Ethernet Port 1 Power ...

Страница 25: ... B Bus A out 5 pin female 2 Rightmost A Bus B out 4 Rightmost B REF SIGNAL GND OV Vs Bus A out Bus B out Bus A in Bus B in NOTE Profibus cabling required Obey pairing as shown If termination resistor R is enabled on bus out terminals are disabled Communication Bus P Profibus Pinout HS6A WIRING DIAGRAMS Power Supply Bus In Bus Out Pinouts for Profibus Power Bus out Bus in ...

Страница 26: ...INK 4 6 SET ZERO BLUE 9 7 SET DIRECTION RED 8 8 NC 5 NC 6 NC 7 NC 10 REF SIGNAL GND Vs CLK CLK DAT DAT SET ZERO SET DIRECTION NC NC NC NC NOTE Twisted pair cable required with overall shield individual pair shielding recommended Obey pairing as shown Communication Bus S SSI Pinout HS6A WIRING DIAGRAMS Pinouts for SSI Option F M23 12 Option E M12 8 ...

Страница 27: ...HS6A 27 HS6A SSI S 12mm Bore P End Thru Shaft Universal Mounting U Connector M12 8 E ...

Страница 28: ...HS6A 28 HS6A SSI S 15mm Bore R End of Shaft Mounting E Connector M23 12 F ...

Страница 29: ...2 1230 FAX 1 216 642 6037 www avtronencoders com HS6A Profibus DP P 15mm Bore R End of Shaft Mounting E Connector M12x3 C DIMENSIONS IN INCHES MILLIMETERS ALL DIMENSIONS ARE APPROXIMATE Features and specifications subject to change without notice Avtron standard warranty applies All dimensions are in millimeters approx ...

Отзывы: