Installation
Avtron Outdoor Load Bank • Part Number K875A 1035409
3-6
b.
If exhaust duct exits through motorized louvers, the design must be interlocked to
assure full open prior to operation. Consideration must also be given for louver
design and actuator to prevent heat problems.
c.
The fan/blower is designed to move 20,000 cfm per resistor stack. Therefore, if
installed indoors, the building air intake system must be upgraded to provide this
continuous additional 20,000 cfm of free air.
Consult the factory if hoods are not used or if strong prevailing winds exist. Failure to obtain written
factory approval for special intake or exhaust conditions voids warranty.
ADDITIONAL AIRFLOW CONSIDERATIONS
1.
Load Banks mounted into a channel, trough, hollow, well, pit, surrounded completely by a
parapet wall or backed into a full corner require special considerations even if the other
conditions are met. In these cases, provide detailed site layout drawings to Avtron for
inspection and comments.
2.
Locations which have full or partial perimeter fence necessitate a review. The fencing
material should have at least 75% open area. The minimum clearances still apply. Overhead
fencing or grating is not recommended.
3.
Do not install Load Banks or other air handling devices within the same area. Any high
velocity air stream near the Load Bank air flow can disrupt the cooling. This is critical if the
other equipment is a source of heat. Any thermal rise on Load Bank intake air can create a
potential hazard.
4.
The Load Bank cooling system cannot be used for any purpose other than cooling the Load
Bank.
5.
In northern climates with snow depths exceeding 6 inches or blowing and drifting snow, a
physical inspection of the Load Bank intake and exhaust is required prior to operation. Any
significant snow drifts or snow depths must be cleared prior to operation.
6.
Standard Load Banks are designed for operation between sea level and 2,000 feet maximum
altitudes. Operation at altitudes over 2,000 feet above sea level requires special
consideration. As the altitude increases, the effective cooling air diminishes. Contact Avtron
for assistance.
Содержание 1035409
Страница 1: ...K875A 1035409...
Страница 3: ......
Страница 4: ......
Страница 5: ......
Страница 7: ......
Страница 9: ......
Страница 17: ......
Страница 21: ......
Страница 25: ......
Страница 39: ......
Страница 41: ......
Страница 45: ......
Страница 71: ......
Страница 72: ......
Страница 73: ......
Страница 74: ......
Страница 75: ......
Страница 76: ......
Страница 77: ......