Room Alert S Models (RA32S-DAP-RAS & RA12S-DAP-RAS)
Tip
3. If your SNMP monitoring application uses SNMPv3, select
Use SNMPv3
; otherwise,
leave this box un-checked.
SNMP Configuration v1 &v2c
To begin configuring your Room Alert for SNMP v1 or v2c:
1. In
Community Name
, you may leave the default SNMP protocol community name,
“public,” or enter a new name.
Tip
2. You may leave
Contact (sysContact)
blank or enter a person’s name to specify who is
receiving the information.
3. You may leave
Location (sysLocation)
blank or enter the location of your Room Alert
monitor.
4. Select
Save Settings
at the top or bottom of the page. Your Room Alert will
automatically reboot and commit your changes.
SNMP Configuration v3
After you select
Use SNMPv3
, you’ll see new options appear on the SNMP Settings page. To
begin configuring your Room Alert for SNMP v3:
1. Select a
Security Level
from the drop-down menu. The default is No authentication or
privacy.
2. If you select
With authentication but no privacy
or
With authentication and
privacy
, you’ll see some or all of these additional fields:
• In
Username
, enter the username that’s configured in your SNMP monitoring
program.
• In
Authorization Protocol
, select the protocol that your SNMP monitoring program is
Room Alert sends values to your 3
rd
-party SNMP monitoring application in 4-digit
format by default. 78.55° F, for example, appears as 7855. In 2-digit format,
your values are truncated, not rounded to the nearest number. In this example,
78.55 would appear as 78.
The community name you assign here must match the one in your 3
rd
-party
SNMP monitoring application.