Flood Sensor - Cable (RMA-F008-SEN & RMA-F024-SEN)

Sensor Features & Specifications

Environment Condition Monitored

Presence/absence of liquid

Type Of Sensor

Switch

     

Flood Detection Switch Port

          Normal State

Closed (Liquid NOT detected)

          Alarm State

Open (Liquid detected)

     

Cable Fault Detection Switch Port

          Normal State

Closed (No cable fault)

          Alarm State

Open (Cable fault)

Power Supply

AVTECH 5V power adapter

Sensor Cable Type

     

2-wire low-voltage speaker wire

          Included

Yes

          Length

25' (7.6 m)

          Maximum Extendible Length

900' (274.3 m)

     

RJ-11 leader

          Included

Yes, built-in

          Length

25' (7.6 m)

          Maximum Extendible Length

100' (30.5 m)

    

 Flood Cable

          Included

Yes

          Length

8' (2.4 m), 24' (7.3 m) and custom lengths available

Compatible Products

Any Room Alert model

Previous Generation Flood Sensor Cable

In the previous generation of Flood Sensor Cable, the orange-twisted Flood Cable and 

the RJ-11 leader are separate components that must be fitted together. To assemble the 

previous generation Flood Sensor Cable:

•  Connect the 4-pin custom jack 

on the orange twisted Flood 

Cable to the matching port on 

the RJ-11 leader.

• 

Screw the cover down on the plastic threads for a secure fit.

When the orange-twisted Flood Cable is disconnected from the RJ-11 leader cable, the 

Cable Fault Detection port’s switch state will read as Open.

AVT-180309-2.0.0

Содержание RMA-F008-SEN

Страница 1: ...re One 1 AVTECH 5V power adapter Two 2 mounting screws Flood Sensor Box Cable Fault Detection Port Flood Detection Port Right Status LED Power Port Left Front RJ 11 Leader Port Flood Sensor Cable Features Switch Ports Flood Detection Port Use this port to monitor the presence absence of liquid Its switch state becomes Open alarm state when liquid is detected Cable Fault Detection Port Optional use...

Страница 2: ...ome in contact with liquid The box itself plugs into main power and must stay dry 1 Locate the Flood Sensor box away from water and above any anticipated water line the box itself plugs into main power and must stay dry You may mount it using the two included mounting screws 2 Run the orange twisted Flood Cable where water is most likely to run or settle Step 2 Connect the Flood Sensor Cable to th...

Страница 3: ...t The leads are non polarized so you may connect either lead to either side of the open port Step 4 Connect your Flood Sensor Cable to a power source Use only the AVTECH 5V power adapter Others may damage the sensor 1 Connect the included power adapter to the power port on the Flood Sensor box 2 Then insert the power adapter plug in to a power source Notice that the Status LED lights up when the b...

Страница 4: ... in Length 25 7 6 m Maximum Extendible Length 100 30 5 m Flood Cable Included Yes Length 8 2 4 m 24 7 3 m and custom lengths available Compatible Products Any Room Alert model Previous Generation Flood Sensor Cable In the previous generation of Flood Sensor Cable the orange twisted Flood Cable and the RJ 11 leader are separate components that must be fitted together To assemble the previous genera...

Страница 5: ...X Label you may leave the default Switch Sen X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods 4 In Alarm On select the alarm state Open or Closed for your switch sensor You may find the alarm state of your switch sensor under the Features Specifications section of this Install...

Отзывы: