background image

  

 

Page 2 

Flood Sensor - Cable (RMA-F008-SEN & RMA-F024-SEN)

Switch Port

CLOSED means...

OPEN means...

Flood Detection

Liquid NOT detected (normal)

Liquid detected (alarm)

Cable Fault Detection (Optional)

No cable fault (normal)

Cable fault (alarm)

Status LED

The Status LED indicates the state of the Flood Sensor:

Appearance

Means...

Lit solid

Liquid NOT detected (normal)

Blinking steadily

Liquid detected (alarm)

Double blink (blink twice/pause/blink twice/etc.)

Flood Sensor Cable disconnected

Install Your Flood Sensor - Cable

Do not use this sensor in hazardous (classified) locations or life safety applications. 

Step 1: Mount your Flood Sensor - Cable.

Do not allow the Flood Sensor box to come in contact with liquid. The box itself plugs 

into main power and must stay dry.

1.  Locate the Flood Sensor box away from water and above any anticipated water line—

the box itself plugs into main power and must stay dry. You may mount it using the 

two included mounting screws.

2.  Run the orange-twisted Flood Cable where water is most likely to run or settle.

Step 2: Connect the Flood Sensor Cable to the Flood Sensor box.

Connect the RJ-11 leader to the RJ-11 port on the Flood Sensor box. 

Try to avoid running the leader cable near large electromagnetic 

devices or fluorescent lights, which produce EMI and can interfere with 

sensor readings.

Step 3: Connect the Flood Sensor box to the Room Alert Monitor.

Do not connect the switch sensor inputs (dry contacts) on AVTECH products to any live 

circuit.

Use only low-voltage 2-wire cable to connect switch sensor inputs.

Содержание RMA-F008-SEN

Страница 1: ...re One 1 AVTECH 5V power adapter Two 2 mounting screws Flood Sensor Box Cable Fault Detection Port Flood Detection Port Right Status LED Power Port Left Front RJ 11 Leader Port Flood Sensor Cable Features Switch Ports Flood Detection Port Use this port to monitor the presence absence of liquid Its switch state becomes Open alarm state when liquid is detected Cable Fault Detection Port Optional use...

Страница 2: ...ome in contact with liquid The box itself plugs into main power and must stay dry 1 Locate the Flood Sensor box away from water and above any anticipated water line the box itself plugs into main power and must stay dry You may mount it using the two included mounting screws 2 Run the orange twisted Flood Cable where water is most likely to run or settle Step 2 Connect the Flood Sensor Cable to th...

Страница 3: ...t The leads are non polarized so you may connect either lead to either side of the open port Step 4 Connect your Flood Sensor Cable to a power source Use only the AVTECH 5V power adapter Others may damage the sensor 1 Connect the included power adapter to the power port on the Flood Sensor box 2 Then insert the power adapter plug in to a power source Notice that the Status LED lights up when the b...

Страница 4: ... in Length 25 7 6 m Maximum Extendible Length 100 30 5 m Flood Cable Included Yes Length 8 2 4 m 24 7 3 m and custom lengths available Compatible Products Any Room Alert model Previous Generation Flood Sensor Cable In the previous generation of Flood Sensor Cable the orange twisted Flood Cable and the RJ 11 leader are separate components that must be fitted together To assemble the previous genera...

Страница 5: ...X Label you may leave the default Switch Sen X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods 4 In Alarm On select the alarm state Open or Closed for your switch sensor You may find the alarm state of your switch sensor under the Features Specifications section of this Install...

Отзывы: