Page 3
Current Loop 1 & 2 (RMA-CL1-SEN & RMA-CL2-SEN)
Early versions of the Room Alert 12E have this polarity reversed: LEFT = negative (-),
and RIGHT = positive (+). If you observe your voltage value flipping back and forth
from “0” to “5,” it’s likely that the speaker wires simply need to be inserted in the
opposite contact.
Room Alert models 32E and 12E have built-in analog input ports; Room Alert models 32E,
24E, 12E, 4E & 3E can also interface with analog sensors through AVTECH’s Temperature
& Analog Sensor, which connects to Room Alert’s Digital Port. For more information
about AVTECH’s Temperature & Analog Sensor, please see its Installation Note, visit
or contact a Product Specialist.
Sensor Features & Specifications
Environment Condition Monitored
Electrical current (amps)
Type Of Sensor
Analog
Power Supply
Induced from monitored conductor
Sensor Cable Type
Low-voltage 2-wire speaker cable
Included
Yes
Length
25'
Maximum Extendible Length
100'
Output Voltage
0 to 5 VDC
Input Amperage Range
Current Loop 1 (RMA-CL1-SEN)
0 to 50 A
Current Loop 2 (RMA-CL2-SEN)
0 to 250 A
Accuracy
+/- 1.0% (2 to 100% FSO)
Response Time
< 100 mS
Operating Frequency Range
50 to 600 Hz
Isolation Voltage
2,200 VAC
Maximum Sensing Current Voltage
600 VAC
Apeture (Hole) Size
0.75" (Accepts cables up to 350 MCM)
DIN Rail Size
35 mm
Operating Temperature
-15 to 40º C (5 to 104º F)
Operating Humdity
0 to 95% RH, non-condensing
Enclosure Rating
UL94-5VB
Compatible Products
Room Alert 32E/W & 12E
Through the built-in Analog Input Port(s),
Room Alert 32E/W, 24E, 12E, 4E & 3E
With a Temperature & Analog Sensor
AVT-171211-3.1.0