background image

enabled, either centralized data logging in the DSView 3 software or data logging in Cyclades OnSite 
console server. DSView 3 software supports data logging of serial sessions or direct SSH/Telnet sessions to 
the appliance. A data log license is required for each enabled data log of serial sessions. DSView 3 software 
ships with 32 available data log licenses. 

 
IV. Firmware Management 

Support for scheduling of firmware uploads to Cyclades OnSite appliances and Cyclades PM power 
management devices from DSView 3 software have been added. 

 
V. Topology 

Synchronization 

Support for pull and push of topology from DSView 3 software and/or Cyclades OnSite appliances has been 
added. 

 
VI.  Save and Restore of Cyclades OnSite configuration 

Support for saving and restoring Cyclades OnSite console server configuration from DSView 3 software has 
been added. 

 
VII. New Syslog Message Format and New Messages 

Support for new format for the Syslog messages plus new Syslog messages have been added. 

 
VIII. Power Management re-design

 

One of the major enhancements made in Cyclades OnSite appliance v3.1.0 is the Power Management re-
design and Third Party Power Management Support. As a result of these two major additions, a few other 
enhancements were added which are listed below: 

 
1. Third Party Power Support 

a. In addition to the Cyclades PM, Cyclades OnSite appliance 3.1.0 supports SPC and ServerTech Switched 
CDU power products. 
b. Both SPC and Server Tech products are managed from DSView 3 software version 3.4. 
c. A license is required to support Server Tech’s Switched CDU products. License activation is done through 
the DSView 3 management software interface. 

 
2. IPDU auto-detection 

a. Once an IPDU is plugged in one of the serial ports configured as “power management”, its speed, type, 
model and name can be automatically detected. 
b. If auto-detection is not enabled, the user will have to specify the IPDU type and speed. 
c. With the IPDU auto detection feature, adding and dropping IPDUs in a daisy chain can be dynamic, 
eliminating the re-configuration and re-association of power outlets. 

 
3. IPDU Status Polling Performance Enhancement 

a. Enhancements have been made so that the new power management design implementation maintains an 
internal cache and allows for IPDU status polling configuration. 
b. Instead of sending requests for information on-demand, the internal information cache is constantly 
updated. This decreases the response time when the user wants to get information about the IPDUs. 
c. In large deployments, this performance enhancement eliminates long waits to receive outlet information 
from OnSite units. 

 
4. Dynamic IPDU Identification 

a. In Cyclades OnSite appliance v3.1.0, each IPDU is assigned with a unique IPDU ID, which will be the 
primary reference for that IPDU. 
b. Outlets will be referred as <IPDU ID>[<outlet number>]. 
c. As IPDU ID configuration is stored in the IPDU, the references to that IPDU in the appliance configuration 
will not change when the IPDU moves to another port or to another position in a daisy-chain. 

 
5. Command synchronization across serial ports 

a. The command line interface (pmCommand) and the menu interface (pmMenu) are not bound to a single 
serial port. Therefore, a single command can be issued to IPDUs connected to different serial ports. 
b. Power cycle commands to outlets from different serial ports are now synchronized (no outlet in the outlet 
list will be turned on until all outlets from the list have been turned off). 

 

Содержание Cyclades OnSite Branch Office Appliances

Страница 1: ...e Plug in version 1 2 0 for DSView 3 software version 3 4 or later to manage Cyclades OnSite appliances Please refer to your DSView 3 software version 3 4 and Cyclades OnSite Plug in version 1 2 0 manual and release notes for detailed configuration instructions II Support for Centralized Authentication Support for Centralized Authentication through DSView 3 software has been added This is in addit...

Страница 2: ...gement software interface 2 IPDU auto detection a Once an IPDU is plugged in one of the serial ports configured as power management its speed type model and name can be automatically detected b If auto detection is not enabled the user will have to specify the IPDU type and speed c With the IPDU auto detection feature adding and dropping IPDUs in a daisy chain can be dynamic eliminating the re con...

Страница 3: ...Sun and any time of the day for Day Light Savings c With the passing of Energy Policy Act of 2005 by the United States Congress which is effective since March 2007 this feature will allow easy configuration of such changes in Day Light Savings laws X Linefeed suppression extended to SSH a Linefeed suppression option was extended to SSH sessions b Configuration is the same as for Telnet sessions wh...

Страница 4: ...r APM v1 4 1 3 When the upgrade operation is performed from DSView 3 software make sure to review the Operation Results It is also recommended that the DSView 3 status polling is disabled when firmware upgrade is run NOTE DO NOT re boot the unit if OnSite firmware upgrade fails It may result into flash corruption 4 Changing the authentication type to from NIS will require the restart of the follow...

Страница 5: ...in telnetd L bin login 7 The etc sudoers file was changed to include commands for DSView 3 software Integration 8 CLI and Web interfaces were modified to support configuration changes in the redesigned Power Management daemon 9 CLI and Web interfaces were modified to support configuration changes in the redesigned Power Management daemon 10 PM Firmware upgrade command pmfwupgrade syntax changed pm...