1.2.1 Battery charger CHARGER 6
The power supply unit is shipped together with:
1. The 230V mains cable equipped with the IEC plug;
2. A temperature sensor;
3. Set of plugs for connecting power supply of VAS amplifiers (6 pcs. of the PC 5/2-ST-1-7 plugs);
4. Set of plugs for connecting power supply of VAS controllers (2 pcs. of the MSTB2,5/2-ST plugs);
5. Set of plugs for connecting inputs and outputs of the indication system
(5 pcs. of the MSTB2,5/2-ST plugs)
A digital display panel, a USB port and 4 LED indication diodes are installed in the front panel of
the power supply unit:
A:
U – battery voltage
B:
IA – current for controllers
C:
IB – current of charge/disacharge
D:
T – battery temperature
1.
Mains -
(green)
2.
Battery
- (yellow)
3.
Charging
- (green)
4.
Fault
-
(yellow)
Fig. 3 View of the front and back panel of the
CHARGER 6
power supply unit
The back panel contains:
1. A male IEC socket for connecting the mains cable (230Vac 50Hz).
2. Four screw connectors for connecting two 24 V battery banks (BAT1, BAT2) and two
neighbouring connectors of the circuit equalizing voltages of the battery banks M.
3. A socket for connecting the temperature sensor (TEMP SENSOR).
4. Two input sockets for external fault indication (EXT. FAULT 1 and EXT. FAULT 2).
5. Three output sockets of relay indication system (MAINS FAULT, BATTERY FAULT and GENERAL
FAULT).
6. 6 sockets for connecting VAS 24V amplifiers (from OUT1 to OUT6). They can also be used for
connecting the heat and smoke control system.
7. A double socket for connecting the network controller and other VAS modules designed for
work with 24V power supply (ADDITIONAL OUTPUT 24V).
8. LEDs to monitor output conditions of high current outputs
9. LEDs to monitor output conditions of high AUX outputs
10. Connector “M” for battery balancer
11. Primary fuse 6.3 AF
12. Ethernet connector. ( optional )
D
C
B
A
1
2
3
4
2
8 6
2
A
1
7
5
4
3
9
11
10