4.5 

Operation state signaling 

The power supply is equipped with LED, sound and remote indication systems. The LED indication is 
used in order to bring attention of the personnel to the operation state of the device and to inform 
about the reason of a potential malfunction. The sound indication system is activated together with 
the lighting signalling. 
Fault indication is maintained as active until it is deactivated using the vertical arrow button located in 
the display panel. Short press of the button switches the sound indication system off, while keeping 
the LED and remote indication systems active. The remaining indication systems can be deactivated 
by pressing and holding the vertical arrow button for over 5 seconds. However, the use of the key is 
effective only when the reason triggering the event generation is no longer present. The indication 
systems are reset automatically only when the network power supply is restored and external signals 
at the 

EXT. FAULT 1

 and 

EXT. FAULT 2

 inputs are no longer detected. In the case of the power failure, 

instead of a continuous sound signal, a short, intermittent signal is generated every 15 seconds. 
The LED indication system comprises four LED diodes located in the front panel of the power supply. 
Three diodes represent the current operation mode (

MAINS

 - green, 

BATTERY 

- yellow, 

CHARGING

 - 

green), and the fourth - fault (

FAULT

 - yellow).  

The remote indication system includes three sockets denoted MAINS FAULT, BATTERY FAULT and 
GENERAL FAULT. Each of the sockets has three plugs, switched between by using relays, completely 
separated from all other circuits. During normal, correct operation of the power supply unit, relay 
coils are active. It means that Mains Fault (power failure) indication, Battery Fault and General Fault 
indications are executed by switching the appropriate relay off (current loss in the relay coil). 
The contact setting in this state (so called zero-voltage state) has been presented next to each 
corresponding

 socket. 

List of states of the LED and remote indication systems is presented in the tables below. 

LED indication system in the front panel. 

DESCRIPTION 

COLOUR 

STATE 

EVENT DESCRIPTION 

MAINS 

green 

on 

Normal operation state at the mains present. 

off 

No mains or rectifier fault. 

BATTERY 

yellow 

on 

Battery operation (no mains or rectifier fault). 

off 

Normal operation state at the mains present. 

CHARGING 

green 

pulsating 

Bulk charging. 

on 

Charging during floating mode (after the bulk 
charging has finished). 

off 

Charging has finished. 

FAULT 

yellow 

on 

Fault occurred within the power supply unit or 
external fault. Please read the error code from the 
display in order to determine the reason. 

pulsating 

External fault indication at 

EXT. FAULT 1 

or 

EXT. FAULT 

2

 input. 

*).

 

*) If it is sent together with the external fault indication an internal fault occurs, the LED diode 

FAULT

 

 will be on continuously. 

Содержание CHARGER 12

Страница 1: ...ish page 1 of 22 CHARGER 6 12 CHARGER 6 Emergency Power Supply CHARGER 12 Emergency Power Supply Battery charger for use in Voice Alarm Systems VAS and Sound Systems for Emergency Purposes SSEP Manual english Rel 1 3c 190320 march 2019 s ...

Страница 2: ...ng device doing so poses a risk of an electric shock or burns Protect the device from the possibility of any items or fluids entering in doing so poses a risk of electric shock and device damage Do not cover ventilation openings doing so may result in device damage Provide a free space of at least 10 cm at the sides of the device enabling its proper ventilation The device must be supplied from mai...

Страница 3: ...9 2 Operation principle 10 3 Installation and connection 13 3 1 Installation 13 3 2 Connection 13 4 Operation 15 4 1 General information 15 4 2 Operation safety 15 4 3 Digitale display 15 4 4 Digitale communication 15 4 5 Operation state signaling 16 4 6 Maintenance 17 5 Servicing 18 5 1 Circuit breakers 18 5 2 Detecting faults and troubleshooting 19 6 Additional information 19 6 1 Remarks of the ...

Страница 4: ...ower for acoustic amplifiers and controllers and other VAS modules separately CHARGER 6 providing 6 2 outputs cooperating with one or two battery banks CHARGER 12 providing 12 4 outputs cooperating with one or two battery banks 1 2 construction The Power supplies are designed for installation in a typical 19 rack and are assembled within a metal case CHARGER 6 19 1 U 1 unit rackspace CHARGER 12 19...

Страница 5: ...Charger 6 Charger 12 rel 1 3c E english page 5 of 22 Fig 1 View and nominal dimensions of CHARGER 6 power supplies Fig 2 View and nominal dimensions of CHARGER 12 power supplies ...

Страница 6: ...e CHARGER 6 power supply unit The back panel contains 1 A male IEC socket for connecting the mains cable 230Vac 50Hz 2 Four screw connectors for connecting two 24 V battery banks BAT1 BAT2 and two neighbouring connectors of the circuit equalizing voltages of the battery banks M 3 A socket for connecting the temperature sensor TEMP SENSOR 4 Two input sockets for external fault indication EXT FAULT ...

Страница 7: ...ntrollers 4 pcs of the MSTB2 5 2 ST plugs 5 Set of plugs for connecting inputs and outputs of the indication system 5 pcs of the MSTB2 5 2 ST plugs A digital display panel a USB port and 4 LED indication diodes are installed in the front panel of the power supply unit A U battery voltage B IA current for controllers C IB current of charge disacharge D T battery temperature 1 Mains green 2 Battery ...

Страница 8: ...OR 4 Two input sockets for external fault indication EXT FAULT 1 and EXT FAULT 2 5 Three output sockets of relay indication system MAINS FAULT BATTERY FAULT and GENERAL FAULT 6 12 sockets for connecting VAS 24V amplifiers from OUT1 to OUT12 7 4 sockets AUX 1 AUX 4 for connecting controllers and other VAS modules designed for work with 24V power supply ADDITIONAL OUTPUT 24V 8 LEDs to monitor output...

Страница 9: ...y output provided for network controller and other VAS modules 1x6 A 2x6 A The quiescent current consumption from the battery 400 mA 800 mA Current consumption from the batteries after LVD disconnection 5m A 5m A Range of output voltage 3 21 0 28 8 V 21 0 28 8 V Maximum current which the power supply unit can take from a single battery when the main power supply is cut off or disconnected A 90 A 9...

Страница 10: ...ndication relays accessible in the back panel The relays are activated when no fault indications are being generated it means that a fault indication causes deactivation of the relay The power supply circuit is based on a direct floating mode system The power supply supplied from the mains is connected in parallel with an external battery bank The VAS amplifiers supplied with their own power suppl...

Страница 11: ...Charger 6 Charger 12 rel 1 3c E english page 11 of 22 Fig 5b Block diagram of CHARGER 12 power supply ...

Страница 12: ...short circuit in the battery circuit supplying power to the additional outputs from the rectifier Measurement of battery circuit resistance is an additional function of the controller The resistance measurement takes place only in the floating mode operation Detection of battery circuit resistance increase caused by an increase in internal resistance of the battery or by an increase of battery con...

Страница 13: ... requires guide bars to be used Guide bars supporting the power supply cassette should be installed in such a way as not to impede the flow of air to the fans located on the both sides of the cassette A 10 cm ventilation space is required on both sides of the case The power supply is not equipped with its own mains switch thus it is necessary to use an adequate switch in the power supply circuits ...

Страница 14: ...e center of the appropriate battery string by means of the cables of the cross section of 0 75mm2 The connection must be protected near the battery with its own fuse of 0 5 2AF Note If only single battery path is used so connect to Bat1 If two battery pathes were used so connect to Bat1 and Bat2 If three battery pathes were used so connect to Bat 1 Bat2 and Bat3 Minimum Akku capacity is 45Ah recom...

Страница 15: ...y bank U its charging or discharging current IB current consumed by the VAS controllers from the 24V power supply IO and of the ambient temperature T if the temperature sensor has been connected The current measurement type selected by using the vertical arrow button is distinguished by switching on a LED diode with the corresponding marking In addition one can read the error code detected by the ...

Страница 16: ...ion mode MAINS green BATTERY yellow CHARGING green and the fourth fault FAULT yellow The remote indication system includes three sockets denoted MAINS FAULT BATTERY FAULT and GENERAL FAULT Each of the sockets has three plugs switched between by using relays completely separated from all other circuits During normal correct operation of the power supply unit relay coils are active It means that Mai...

Страница 17: ...ts off Output switched on Relay indication system DESCRIPTION STATE EVENT DESCRIPTION MAINS FAULT on Normal operation state at the mains present off No mains or rectifier fault BATTERY FAULT on Correct battery operation off High resistance of battery circuit or battery voltage below a preset level battery discharged GENERAL FAULT on No fault off Fault within the power supply or external fault 4 6 ...

Страница 18: ...ly after disconnected the mains and from the battery bank The VAS system personnel can exchange the above mentioned fuses only If other circuit breakers used within the power supply unit are faulty a repair performed by qualified service personnel is required Fig 6 below presents location of the fuses inside the power supplies D L1 00 TR 2 01 P 248 2 B 20 0 1 2 14 1 8 8 7 1 K 301 K 30 0 P 436 1 Fi...

Страница 19: ...akers are accessible directly on the rear panels of the power supplies The VAS power output breakers replacement requires the access described in the point 5 1 Warranty and after warranty repairs are performed by service of the manufacturer or by an authorized service partner of the manufacturer 6 Additional information 6 1 Remarks of the manufacturer The manufacturer reserves the right to introdu...

Страница 20: ...or battery series 1 exceeded E25 Permissible resistance level for battery series 2 exceeded E26 Permissible resistance level for battery series 3 exceeded E27 Permissible resistance level for battery series 4 exceeded E28 Battery 1 configuration error E29 Battery 2 configuration error E30 Battery 3 configuration error E31 Battery 4 configuration error E32 No communication with the output package 1...

Страница 21: ...f non hazardous materials wood paper cardboard plastics which can be recycled Packages which are no longer needed should be passed on to a waste collection station after they had been sorted The used product is a non hazardous waste which should not be disposed of in the general waste bin but it has to be transferred to the local waste collection recycling station accepting electric and electronic...

Страница 22: ...Charger 6 Charger 12 rel 1 3c E english page 22 of 22 ...

Отзывы: