Single Low Intensity Obstruction Light
AV-OL-LI
General Purpose Inputs and Outputs
The AV-OL-LI fixture supports a minimum of five discrete IOs via General Purpose Inputs (2) and Outputs (3) in order
to meet monitoring requirements as well as provide compatibility with our obstruction lighting controllers.
The I/O configurations must be specified at the time of order.
• General Purpose Inputs (GPI1 and GPI2)
Available Input Type
Description
Disabled
The input line will not be monitored.
Photcell Control
The input line is used to control the state of the photocell/light sensor.
Input Low = Night
Input High = Day
OpMode Control
The input line Is used to control the operation mode used by the lantern.
Input Low = Always On
Input High = Day and Night
• General Purpose Outputs (GPO1,GPO2 and GPO3)
Available Output Type Description
Disabled
The output line will remain inactive
Photocell Status
The output line will show the status of the photocell/light sensor.
Open Contact = Night
Closed Contact = Day
LED Fault
The output line will show the fault state of the LED monitoring.
Open Contact = Fault
Closed Contact = OK
Visible LED Fault
IR/NVR LED Fault
GPS Sync
The output line will show the state of the GPS synchronisation.
Open Contact = Not Synchronised
Closed Contact = Synchronised
7.3 Testing Procedure
Note:
Avlite recommends that all testing be done during the day.
Check function of the LI by carrying out the following:
a.
Night mode test: Cover the LI fixture and check night operation is functioning as expected. The LI should either
flash red (for ICAO Type E or FAA L-810(F)) or operate as a red, steady burning light (for ICAO Type A and B or FAA
L-810).
b.
Day mode test: Uncover the LI fixture and check day operation is functioning as expected. The LI should no longer
be illuminated.