13
13
Menu Sections
Relay Modes
The relay contact on a Memcom
+
can be used to switch the power
supply to an external device. The following modes are available:
Pri.rly.mode
Siren
û
ü
Relay contacts close when the Alarm Push is
activated, and open again after the alarm push delay.
Typically used to trigger a siren on the lift car.
Door (NO/CMD)
û
ü
Door release mode, release on command, default
relay state is N/O: The door release is only activated
if the operator presses the ‘8’ key on their handset
during the initial alarm call or any follow-up calls. The
release will then remain activated until the call ends.
Door (NC/CMD)
û
ü
Door release mode, release on command, default
relay state is N/C: The door release is only activated
if the operator presses the ‘8’ key on their handset
during the initial alarm call or any follow-up calls. The
release will then remain activated until the call ends.
Door (NO/ALM)
û
ü
Door release mode, release on alarm push, default
relay state is N/O. The door release is activated
as soon as the Alarm Pictogram is lit, and remains
activated until the End of Alarm signal is received.
Door (NC/ALM)
û
ü
Door release mode, release on alarm push, default
relay state is N/C. The door release is activated
as soon as the Alarm Pictogram is lit, and remains
activated until the End of Alarm signal is received.
PSTN fault
û
ü
The relay contacts default to closed, and open
whenever a PSTN line fault is detected. When the
fault condition is cleared, the contacts return to the
default closed state.
GSM fault
ü
The relay contacts default to closed, and open
whenever a GSM fault is detected. When the fault
condition is cleared, the contacts return to the default
closed state.
Note: GSM monitoring must first be setup under ‘HW
monitoring.
Tech. fault
û
ü
Technical fault mode - The relay contacts default to
the closed state, opening whenever any technical
fault is detected by the Memcom
+
. Once the fault
condition has cleared, the contacts close again.
Emg. Lighting
û
ü
Emergency lighting mode - the relay contacts default
to the open state, closing within 1 second of a loss
of external power. This allows the use of the relay to
switch backup power to emergency lighting hardware
during an external power failure. Once external power
is restored, the relay contacts open again.
Spk. Picto
û
ü
If a dual illuminated alarm push is connected to the
relay contacts:
When the call centre answers an alarm call the relay
contact will close and trigger the illumination on the
alarm push; alarm push will remain lit until the call
centre ends the call.
Both Pictos
û
ü
If a dual illuminated alarm push is connected to the
relay contacts:
When the alarm button is pressed the relay contact
will close triggering the illumination on the alarm
push; alarm push will remain lit until the call centre
ends the call.
Low battery
û
ü
Defaults to holding the contacts closed, opening
them when a low battery state is detected.
Pri.rly.o/ride
None
û
ü
Enables the state of the primary relay contacts to
be overridden to open or close regardless of the
operation mode setting.
Open
û
ü
Closed
û
ü
Full Programming Options
GMT Offset
For reference only; will not need updating on the unit.
DTMF RX
Use only if directed by Avire Technical Support.