disturbances.
Note: the Installer can reverse the use of two settings (OUTDOOR to the
Indoor of a building, and INDOOR for outdoor use) if the Installer detects
an external site where there is a low possibility of interference, or an
internal site where there is high possibility of false alarm.
CROSSING / APPROACH
- Dip Switch n° 3 in pos OFF Crossing
/ in pos ON Approach
In a Barrier protection is necessary to establish at the time of
installation, which will be the transit direction of the intruder in
reference of the barrier. The two settings are then optimized to
exploit the different characteristics of the two detection sensors
(MW and IR) in these two different situations of detection.
Considerations about the selectable sensitivities :
Using the dip switch No. 2 and No. 3 will have 4 different sensitiv-
ity of detection that have been optimized for operation in installa-
tions for outdoor or indoor, with movements that approaching the
sensor, or crossing its detection lobe .
The levels of sensitivity, sorted by sensing speed (from fastest 1 ^
to slowest ^ 4), are listed in the table below:
1^ Indoor Crossing
2^ Indoor Approach
3^ Outdoor Crossing
4^ Outdoor Approach
LED OFF
DipSwitch N°5 in pos. ON
Disable the views of detection, keeping enabled the views of the
memories.
Tab.1
DISPLAY
Led BLU
Led ROSSO Led GIALLO
MW
ALARM
IR
ANTIMASK
FLASH
FLASH
FLASH
TRIMMER
Adjusts the range of the sensor.
To the adjusting to keep as a reference the range determined
by the microwave (MW). The sensor will automatically adjust the
operation of the Infrared (IR) to this adjustment.
Note: contrary to the microwave, for which it is possible to determine with
sufficient precision its limit of detection, for the infrared this condition is
not applicable.
This is because the infrared detection is affected by ambient temperature,
from clothing of the intruder, the presence / absence of wind, etc.. The
trimmer thus automatically adjusts the detection capability of the Infrared
as a function of the microwave range selected, without necessarily delimit
its field of action as that of the microwave (the Infrared will be automati-
cally configured for the most adverse conditions at that range). You can so
have infrared detections even to greater distance than that defined by the
trimmer without compromising the reliability of the sensor.
FUNCTIONS TROUGHT INPUT LINE
These functions are activated / deactivated by the System arming
ON / System arming OFF.
It is considered:
12V
on INPUT = System arming
OFF
0V
on INPUT = System arming
ON
REMOTE ENABLING LED
REQUEST CONDITION LED OFF
At the System arming OFF, the sensor will arrange for the rehabili-
tation of the views of detection. The views will be rehabilitated at
the first detection, and will remain active for 30sec.
MEMORIES
At System arming OFF, will displayed the memory of the first alarm
occurred, as in Tab. 2.
The memory will be resetted to the next System arming ON.
DELAY of MEMORY for use in TIMED ZONES
Time of Exit: alarms that occur within the first 30sec. from the
System arming ON will be erased.
Time of Entry: alarms that occur 30 sec. before the System
arming OFF will be erased
DECLARATION OF CONFORMITY’
Ave declares that this equipment is compatible
with the essential requirements of Directive 1999/5/EC
SPECIFICATION
Voltage:
12V +/- 3V
Current Max
(in memory of All.):
32mA
Current Stand By:
20mA
Mocrowave:
24 Ghz
Alarm Period:
3 sec
Opto Relay :
100mA / 24V
Tamper:
100mA /30V
Wall Tamper:
300mA / 48V
Operating Temp:
-10°C/+55°C
Ambient umidity:
95%
Teoric MTBF:
120.000 hours
Dimensions:
110 x44 x 46mm
Performance Level:
EN50131-2-4
Grade 2, CLASS IV
Tab.2
MEMORY DISPLAY
Led BLU
Led ROSSO Led GIALLO
PIR+MW
OFF
ON
OFF
ANTIMASK
FLASH
ON
FLASH