INSTALLATION
Avaya
t
Line Interactive RM UPS Site Preparation, Installation and Operator’s Manual
S
164201663 Rev 1
33
Installing the UPS
See Figure 15 and Figure 16 for the UPS rear panels.
To install the UPS:
1.
If you did not mount the UPS in a rack or to a wall, place the UPS in
a flat, horizontal position.
2.
If you are installing power management software, connect your
computer to the USB port or UPS communication port using the
supplied cable (see page 43).
NOTE
If you need to change the factory-set defaults for the output voltage or input voltage
range, see “Voltage Configuration” on page 39 before installing the UPS.
3.
Plug the equipment to be protected into the UPS output
receptacles (see page 41 for more information on load segments).
NOTE
DO NOT protect laser printers with the UPS because of the exceptionally high power
requirements of the heating elements.
4.
For 230V models only.
Plug the detachable power cord into the input
connector on the UPS rear panel.
6-ft Power Cord with
5-15 Plug
Four 5-15 Receptacles
Site Wiring Fault
Indicator
Communication
Port
DIP Switches
Network Transient
Protector
USB Port
X-Slot
Communication Bay
Figure 15. 500–1500 VA, 120V Rear Panel