
SPECIFICATIONS
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
72
Table 15. Electrical Output
Normal Mode
Battery Mode
Voltage Regulation
±2%
Nominal output voltage ±3%
Efficiency
>95% (High Efficiency mode), >88%
>79.5% (700 VA), >82% (1000–1500 VA),
>84% (3000 VA)
Frequency Regulation
Sync with line ±3 Hz of nominal line
frequency (outside this range: ±0.1 Hz of
auto-selected nominal frequency)
±0.1 Hz of auto-selected nominal
frequency
120V Models
208/230/240V Models
Nominal Outputs
100/110/120/127V (voltage configurable
or auto-sensing)
1000/1500/3000 VA
0.9/1.35/2.7 kW
200/208/220/230/240V
(voltage configurable or auto-sensing)
1000/1500/3000 VA
0.9/1.35/2.7 kW
Frequency
50 or 60 Hz, autosensing or configurable as a frequency converter
Output Overload (Normal Mode)
100–102%: Activates Overload alarm. (Level 1)
102–129%: Load transfers to Bypass mode after 12 seconds. (Level 2)
130–149%: Load transfers to Bypass mode after 2 seconds. (Level 3)
>150%: Load transfers to Bypass mode after 100 ms. (Level 4)
NOTE Default configuration transfers immediately to Bypass at >102%.
Output Overload (Bypass Mode)
100–109%: Activates Overload alarm. (Level 1)
110–129%: UPS shuts down after 5 minutes. (Level 2)
130–149%: UPS shuts down after 15 seconds. (Level 3)
>150%: UPS shuts down after 300 ms. (Level 4)
Output Overload (Battery Mode)
100–102%: Activates Overload alarm. (Level 1)
102–129%: UPS shuts down after 12 seconds. (Level 2)
130–149%: UPS shuts down after 2 seconds. (Level 3)
>150%: UPS shuts down after 100 ms. (Level 4)
Voltage Waveform
Sine wave
Harmonic Distortion
<3% THD on linear load; <5% THD on non-linear load
Transfer Time
Online mode: 0 ms (no break)
High Efficiency mode: 10 ms maximum (due to loss of utility)
Power Factor
0.9
Load Crest Factor
3 to 1