
INSTALLATION
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
24
NOTE
A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable
or disconnect it.
NOTE
Leave
ribbon cable
connected.
Figure 8. Removing the UPS Right Front Cover
C A U T I O N
A small amount of arcing may occur when connecting the internal batteries. This is normal
and will not harm personnel. Connect the cables quickly and firmly.
2.
Connect the internal battery connector (see Figure 9).
1000/1500 VA models.
Unclip the top rightmost white connector from
the battery panel and move it to the left to connect to the white
connector at the top left. Connect red to red, and black to black.
Press the two parts tightly together to ensure a proper connection.
Clip the wires of the rightmost connector to the battery panel in its
new position.
3000 VA models.
Connect red to red, and black to black. Press the
two parts tightly together to ensure a proper connection.