Instructions and user manua
l
PANDuo pH Turboxy
NOT044ENV02
12
3.2.7
Installation complete
Default pH values
- Setpoint at pH 7.4
- Dosing of acid reagent to bring the pH down
Default values Chlorine
- Set point at 1.4 Cl (corresponding to 1.4 ppm)
If you would like to obtain a pH of 7.4 and you are dosing with acid, your unit is ready for use without
further preparation. Otherwise, please refer to the following sections to adjust the advanced parameters as
a function of your needs.
CALIBRATING Cl
↑↓1.55 Cl (xxx)
Record the analyzed value in mg / L (ppm)
with a DPD1 photometer or dipstick or pellet
comparator.
The number in parentheses is the current
generated by the chlorine probe. It's just
technical information, do not worry.
Keep pressed for at least 5 seconds
1.2Cl/↑
SET CAL
TIP
PRESS THE
ESC
KEY AT ANY TIME TO EXIT MENU.
After pressing OK, the unit resumes
normal operation
↓ 7.3pH 1.2Cl ↑
Analyze the rate of chlorine with a reactive DPD1 and memorize the obtained value
Take the water near the discharge. Measure the
chlorine Cl level in mg / L (ppm) with a DPD1
photometer or dipstick or pelletizer. Press OK
TAKE WATER NEAR THE DISCHARGE. MEASURE CL WITH PHOTOMETER DPD1 OR OTHER
Press OK
i
At this stage, PAN DUO PH TURBOXY is ready for use without any further adjustments in most
cases.