AUX-DC inverter ARV outdoor unit individual series technical manual
97
3.3 Connection schematic diagram of pipe
Connection Schematic Diagram of system
Allowable
value
Part of pipe
Piping
Length
Overall length of pipe (equivalent length)
1000m
L1+L2+L3+L4+L5+L6+L7+L8+a+b
+c+d+e+f+j+h+i
Max. Equivalent length between outdoor unit and
fastest indoor unit
190m
L1+L5+L6+L7+L8+i
Max. Equivalent length between outdoor unit and
farthest indoor unit
/
For each branch pipe, the
equivalent length of elbow to 0.5m
Max. Equivalent length between indoor unit and
the first Y branch pipe
40/90m
L5+L6+L7+L8+i
Max. piping length between 1st ODU branch and
the farthest outdoor unit
10m
Max. piping length between IDU Branch and
Indoor unit
40m
Level
difference
Level difference
Between ODU & IDU
Outdoor unit is up
90m
/
Outdoor unit is down
110m
/
Level difference among indoor units
30m
/
Содержание ANB66FVAMT
Страница 1: ...AUX DC inverter ARV individual series 1 Technical Manual DC Inverter ARV Individual Series ...
Страница 3: ...AUX DC inverter ARV individual series 3 ...
Страница 19: ...AUX DC inverter ARV outdoor unit individual series technical manual 16 ...
Страница 21: ...AUX DC inverter ARV outdoor unit individual series technical manual 18 ...
Страница 24: ...DC inverter ARV Individual Series technical manual 21 3 3 Wire Diagrams ARV H615 5R1B ARV H670 5R1B ...
Страница 25: ...DC inverter ARV Individual Series technical manual 22 ARV H730 5R1B ARV H780 5R1B ARV H850 5R1B ARV H900 5R1B ...
Страница 27: ...DC inverter ARV Individual Series technical manual 24 3 4Operation limits Cooling mode Heating mode ...
Страница 96: ...AUX DC inverter ARV outdoor unit individual series technical manual 93 ...
Страница 113: ...AUX DC inverter ARV outdoor unit individual series technical manual 110 ...
Страница 127: ...AUX DC inverter ARV outdoor unit individual series technical manual 124 ...