AUX DC Inverter Free Match 50HZ
R32
3. Long piping length
Cooling capacity (KBtu/h)
14K
18K 21K 27K
36K
42K
Connection
Pipe(mm)
Liquid pipe
Φ
6.35*2
Φ
9.52*3
Φ
9.52*4
Φ
9.52*5
Gas pipe
Φ
9.52*2
Φ
15.88*3
Φ
15.88*4
Φ
15.88*5
Max. length for all rooms (m)
40
60
80
Max. length for one IU (m)
25
30
35
Max. height difference
between IU and OU (m)
15
Max. height difference
between IUs (m)
10
Caution:
1. The standard Pipe length is 5m, if the pipe length is less than this then no additional
charging is necessary. If the pipe length is more than this then you should charge more refrigerant
into the system according to the above Charging Data
2. The thickness of the pipe is 0.6-1.0, bearing pressure is 4.2MPa;
3. If the connection pipe is too long, the cooling capacity and stability would be decreased.
And the more bend quantity, the resistance in the piping system would be bigger, then the cooling
and heating capacity would be decreased even lead to compressor broken. We suggest you to
use the shortest connection pipe according to the pipe length parameter in this manual.
If the
height difference between outdoor and indoor unit is more than 5m, an oil trap should be installed
in the gas pipe for every 10 meters.
Содержание AMWM-H07/4R3
Страница 54: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09K 12K 18K 929 660 245 841 205 ...
Страница 57: ...AUX DC Inverter Free Match 50HZ R32 57 5 Outdoor Unit 5 1 14K 18K 545 800 545 822 315 315 ...
Страница 58: ...AUX DC Inverter Free Match 50HZ R32 5 2 21K 27K 834 540 655 854 335 328 ...
Страница 59: ...AUX DC Inverter Free Match 50HZ R32 59 5 3 36K 42K 985 675 808 1000 409 395 ...
Страница 64: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09k 12k 18k ...
Страница 65: ...AUX DC Inverter Free Match 50HZ R32 65 4 Duct 07K 09K 12K 18K ...
Страница 67: ...AUX DC Inverter Free Match 50HZ R32 67 5 1 36K 42K ...
Страница 73: ...AUX DC Inverter Free Match 50HZ R32 73 Part8 Static pressure curve 1 07K 09K Duct ...
Страница 74: ...AUX DC Inverter Free Match 50HZ R32 2 12K Duct ...
Страница 75: ...AUX DC Inverter Free Match 50HZ R32 75 3 18K Duct ...
Страница 81: ...AUX DC Inverter Free Match 50HZ R32 81 ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R32 1 3 F Type 07K 09K 12K 1 2 3 4 5 6 7 8 9 10 11 12 13 15 16 17 18 19 20 21 14 ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R32 5 3 2 1 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ...
Страница 124: ...AUX DC Inverter Free Match 50HZ R32 1 5 F Type 24K 7 9 20 19 1 2 3 4 5 6 8 10 11 12 13 14 16 17 18 15 ...
Страница 135: ...AUX DC Inverter Free Match 50HZ R32 135 2 Cassette 09K 12K 18K ...
Страница 139: ...AUX DC Inverter Free Match 50HZ R32 139 4 Duct 4 1 07K 09K 12K ...
Страница 141: ...AUX DC Inverter Free Match 50HZ R32 141 4 2 18K ...
Страница 143: ...AUX DC Inverter Free Match 50HZ R32 143 5 Outdoor Unit 5 1 14K 18K ...
Страница 145: ...AUX DC Inverter Free Match 50HZ R32 145 ...
Страница 147: ...AUX DC Inverter Free Match 50HZ R32 147 5 3 36K ...
Страница 149: ...AUX DC Inverter Free Match 50HZ R32 149 5 4 42K ...
Страница 155: ...AUX DC Inverter Free Match 50HZ R32 155 4 Cassette 4 1 Installation drawing ...
Страница 160: ...AUX DC Inverter Free Match 50HZ R32 ...
Страница 180: ...AUX DC Inverter Free Match 50HZ R32 Part12 PCB Instruction 1 Outdoor Unit PCB 1 1 14K 18K Main PCB and Driver modular ...
Страница 181: ...AUX DC Inverter Free Match 50HZ R32 181 1 2 21K 27K Main PCB and Driver modular ...
Страница 182: ...AUX DC Inverter Free Match 50HZ R32 1 3 36K 42K Main PCB ...
Страница 183: ...AUX DC Inverter Free Match 50HZ R32 183 Drive Modular Board ...
Страница 184: ...AUX DC Inverter Free Match 50HZ R32 2 Indoor Unit PCB 2 1 09K 12K 18K Cassette ...
Страница 185: ...AUX DC Inverter Free Match 50HZ R32 185 2 2 09K 12K 18K Ceilling Floor ...
Страница 186: ...AUX DC Inverter Free Match 50HZ R32 2 3 07k 09K 12K 18K Duct ...
Страница 189: ...AUX DC Inverter Free Match 50HZ R32 189 2 Failure analysis 2 1 H2 Wired controller communication failure ...
Страница 190: ...AUX DC Inverter Free Match 50HZ R32 2 2 E5 Communication failure between indoor and outdoor unit ...
Страница 191: ...AUX DC Inverter Free Match 50HZ R32 191 Outdoor protection phase sequence ...
Страница 193: ...AUX DC Inverter Free Match 50HZ R32 193 2 4 H6 low pressure protection ...
Страница 194: ...AUX DC Inverter Free Match 50HZ R32 Cooling low pressure protection Heating low pressure protection ...
Страница 195: ...AUX DC Inverter Free Match 50HZ R32 195 2 5 P5 High exhaust temperature protection ...
Страница 196: ...AUX DC Inverter Free Match 50HZ R32 Cooling exhaust temperature protection ...
Страница 197: ...AUX DC Inverter Free Match 50HZ R32 197 Heating exhaust temperature protection ...
Страница 198: ...AUX DC Inverter Free Match 50HZ R32 2 6 H8 four way valve failure protection ...
Страница 199: ...AUX DC Inverter Free Match 50HZ R32 199 2 7 Sensor failure protection ...