AUX DC Inverter Free Match 50HZ
R32
Fahrenheit temperature synchronously.
7.
【
"Child Lock" function display
】
Press both"
∧
" or "
∧
" buttons for more than 5S to enter locking, the controller will display
" " . In the state of locking, operations on the wired controller are disabled (but remote control
receiving is valid).
The method of unlocking:
Press both"
∧
" or "
∧
" buttons for more than 5S or power off the
unit to release the locking (" " does not display).
8.
【
Remote control
】
function
The wired controller can receive remote control commands and update the current status
Start-up the unit with remote controller, wired controller work in accordance with the state set
on the remote controller and displays corresponding working mode;
9. Room temperature sensorequipped on the wired controller
When the wire controller is equipped with a room temperature sensor and the sensor is not
damaged, it is default that the ambient temperature detected by the sensoron the controller and
the temperature value will be sent to the main PCB of the unit.
If the wire controller is not equipped with a room temperature sensor or the sensor is
damaged, the room temperature will be detected by the temperature sensor of the unit itself.
10.Fault display
When the unit has fault, the time bar will directly display the fault code and flash, the display
mode is Er: MM (MM is the fault code, please read the corresponding roduct manual).
Basic condition of wired controller
Name
Figure
Basic condition for operation
Содержание AMWM-H07/4R3
Страница 54: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09K 12K 18K 929 660 245 841 205 ...
Страница 57: ...AUX DC Inverter Free Match 50HZ R32 57 5 Outdoor Unit 5 1 14K 18K 545 800 545 822 315 315 ...
Страница 58: ...AUX DC Inverter Free Match 50HZ R32 5 2 21K 27K 834 540 655 854 335 328 ...
Страница 59: ...AUX DC Inverter Free Match 50HZ R32 59 5 3 36K 42K 985 675 808 1000 409 395 ...
Страница 64: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09k 12k 18k ...
Страница 65: ...AUX DC Inverter Free Match 50HZ R32 65 4 Duct 07K 09K 12K 18K ...
Страница 67: ...AUX DC Inverter Free Match 50HZ R32 67 5 1 36K 42K ...
Страница 73: ...AUX DC Inverter Free Match 50HZ R32 73 Part8 Static pressure curve 1 07K 09K Duct ...
Страница 74: ...AUX DC Inverter Free Match 50HZ R32 2 12K Duct ...
Страница 75: ...AUX DC Inverter Free Match 50HZ R32 75 3 18K Duct ...
Страница 81: ...AUX DC Inverter Free Match 50HZ R32 81 ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R32 1 3 F Type 07K 09K 12K 1 2 3 4 5 6 7 8 9 10 11 12 13 15 16 17 18 19 20 21 14 ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R32 5 3 2 1 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ...
Страница 124: ...AUX DC Inverter Free Match 50HZ R32 1 5 F Type 24K 7 9 20 19 1 2 3 4 5 6 8 10 11 12 13 14 16 17 18 15 ...
Страница 135: ...AUX DC Inverter Free Match 50HZ R32 135 2 Cassette 09K 12K 18K ...
Страница 139: ...AUX DC Inverter Free Match 50HZ R32 139 4 Duct 4 1 07K 09K 12K ...
Страница 141: ...AUX DC Inverter Free Match 50HZ R32 141 4 2 18K ...
Страница 143: ...AUX DC Inverter Free Match 50HZ R32 143 5 Outdoor Unit 5 1 14K 18K ...
Страница 145: ...AUX DC Inverter Free Match 50HZ R32 145 ...
Страница 147: ...AUX DC Inverter Free Match 50HZ R32 147 5 3 36K ...
Страница 149: ...AUX DC Inverter Free Match 50HZ R32 149 5 4 42K ...
Страница 155: ...AUX DC Inverter Free Match 50HZ R32 155 4 Cassette 4 1 Installation drawing ...
Страница 160: ...AUX DC Inverter Free Match 50HZ R32 ...
Страница 180: ...AUX DC Inverter Free Match 50HZ R32 Part12 PCB Instruction 1 Outdoor Unit PCB 1 1 14K 18K Main PCB and Driver modular ...
Страница 181: ...AUX DC Inverter Free Match 50HZ R32 181 1 2 21K 27K Main PCB and Driver modular ...
Страница 182: ...AUX DC Inverter Free Match 50HZ R32 1 3 36K 42K Main PCB ...
Страница 183: ...AUX DC Inverter Free Match 50HZ R32 183 Drive Modular Board ...
Страница 184: ...AUX DC Inverter Free Match 50HZ R32 2 Indoor Unit PCB 2 1 09K 12K 18K Cassette ...
Страница 185: ...AUX DC Inverter Free Match 50HZ R32 185 2 2 09K 12K 18K Ceilling Floor ...
Страница 186: ...AUX DC Inverter Free Match 50HZ R32 2 3 07k 09K 12K 18K Duct ...
Страница 189: ...AUX DC Inverter Free Match 50HZ R32 189 2 Failure analysis 2 1 H2 Wired controller communication failure ...
Страница 190: ...AUX DC Inverter Free Match 50HZ R32 2 2 E5 Communication failure between indoor and outdoor unit ...
Страница 191: ...AUX DC Inverter Free Match 50HZ R32 191 Outdoor protection phase sequence ...
Страница 193: ...AUX DC Inverter Free Match 50HZ R32 193 2 4 H6 low pressure protection ...
Страница 194: ...AUX DC Inverter Free Match 50HZ R32 Cooling low pressure protection Heating low pressure protection ...
Страница 195: ...AUX DC Inverter Free Match 50HZ R32 195 2 5 P5 High exhaust temperature protection ...
Страница 196: ...AUX DC Inverter Free Match 50HZ R32 Cooling exhaust temperature protection ...
Страница 197: ...AUX DC Inverter Free Match 50HZ R32 197 Heating exhaust temperature protection ...
Страница 198: ...AUX DC Inverter Free Match 50HZ R32 2 6 H8 four way valve failure protection ...
Страница 199: ...AUX DC Inverter Free Match 50HZ R32 199 2 7 Sensor failure protection ...