AUX DC Inverter Free Match 50HZ
R32
Notes
Drainage pipe and connection piping should be wrapped by heat insulation material
respectively lift the air conditioner is proved my dew conditioner experiment. But if it keeps on
working in high humidity (the dew temperature is more than23
℃
) environment which may lead to
water leakage, please use following additional insulation material:
◇
Glass fiber insulation material with the thickness between 10~20mm can be used.
◇
The part of indoor unit which get in touch with the back side of ceiling should pasted with
insulation material.
◇
Besides the previous more than 8mm thick insulation material, connection piping (both gas
pipe and liquid pipe), drainage pipe should be wrapped by additional 10~30 mm thick insulation
material.
Seal the hole on the wall.
◇
To prevent rainwater or other foreign bodies from entering the room and air-conditioner, the
gap between wall hole and tubing, drain pipe and electric wire should be sealed with mastic,
sealant rubber or putty.
◇
If the outdoor unit is higher than indoor unit, tubing should be bent to ensure that the lowest
point of the tubing is lower than the wall hole to prevent rainwater entering the room or
air-conditioner along the piping system.
Содержание AMWM-H07/4R3
Страница 54: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09K 12K 18K 929 660 245 841 205 ...
Страница 57: ...AUX DC Inverter Free Match 50HZ R32 57 5 Outdoor Unit 5 1 14K 18K 545 800 545 822 315 315 ...
Страница 58: ...AUX DC Inverter Free Match 50HZ R32 5 2 21K 27K 834 540 655 854 335 328 ...
Страница 59: ...AUX DC Inverter Free Match 50HZ R32 59 5 3 36K 42K 985 675 808 1000 409 395 ...
Страница 64: ...AUX DC Inverter Free Match 50HZ R32 3 Ceiling Floor 09k 12k 18k ...
Страница 65: ...AUX DC Inverter Free Match 50HZ R32 65 4 Duct 07K 09K 12K 18K ...
Страница 67: ...AUX DC Inverter Free Match 50HZ R32 67 5 1 36K 42K ...
Страница 73: ...AUX DC Inverter Free Match 50HZ R32 73 Part8 Static pressure curve 1 07K 09K Duct ...
Страница 74: ...AUX DC Inverter Free Match 50HZ R32 2 12K Duct ...
Страница 75: ...AUX DC Inverter Free Match 50HZ R32 75 3 18K Duct ...
Страница 81: ...AUX DC Inverter Free Match 50HZ R32 81 ...
Страница 120: ...AUX DC Inverter Free Match 50HZ R32 1 3 F Type 07K 09K 12K 1 2 3 4 5 6 7 8 9 10 11 12 13 15 16 17 18 19 20 21 14 ...
Страница 122: ...AUX DC Inverter Free Match 50HZ R32 5 3 2 1 4 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 ...
Страница 124: ...AUX DC Inverter Free Match 50HZ R32 1 5 F Type 24K 7 9 20 19 1 2 3 4 5 6 8 10 11 12 13 14 16 17 18 15 ...
Страница 135: ...AUX DC Inverter Free Match 50HZ R32 135 2 Cassette 09K 12K 18K ...
Страница 139: ...AUX DC Inverter Free Match 50HZ R32 139 4 Duct 4 1 07K 09K 12K ...
Страница 141: ...AUX DC Inverter Free Match 50HZ R32 141 4 2 18K ...
Страница 143: ...AUX DC Inverter Free Match 50HZ R32 143 5 Outdoor Unit 5 1 14K 18K ...
Страница 145: ...AUX DC Inverter Free Match 50HZ R32 145 ...
Страница 147: ...AUX DC Inverter Free Match 50HZ R32 147 5 3 36K ...
Страница 149: ...AUX DC Inverter Free Match 50HZ R32 149 5 4 42K ...
Страница 155: ...AUX DC Inverter Free Match 50HZ R32 155 4 Cassette 4 1 Installation drawing ...
Страница 160: ...AUX DC Inverter Free Match 50HZ R32 ...
Страница 180: ...AUX DC Inverter Free Match 50HZ R32 Part12 PCB Instruction 1 Outdoor Unit PCB 1 1 14K 18K Main PCB and Driver modular ...
Страница 181: ...AUX DC Inverter Free Match 50HZ R32 181 1 2 21K 27K Main PCB and Driver modular ...
Страница 182: ...AUX DC Inverter Free Match 50HZ R32 1 3 36K 42K Main PCB ...
Страница 183: ...AUX DC Inverter Free Match 50HZ R32 183 Drive Modular Board ...
Страница 184: ...AUX DC Inverter Free Match 50HZ R32 2 Indoor Unit PCB 2 1 09K 12K 18K Cassette ...
Страница 185: ...AUX DC Inverter Free Match 50HZ R32 185 2 2 09K 12K 18K Ceilling Floor ...
Страница 186: ...AUX DC Inverter Free Match 50HZ R32 2 3 07k 09K 12K 18K Duct ...
Страница 189: ...AUX DC Inverter Free Match 50HZ R32 189 2 Failure analysis 2 1 H2 Wired controller communication failure ...
Страница 190: ...AUX DC Inverter Free Match 50HZ R32 2 2 E5 Communication failure between indoor and outdoor unit ...
Страница 191: ...AUX DC Inverter Free Match 50HZ R32 191 Outdoor protection phase sequence ...
Страница 193: ...AUX DC Inverter Free Match 50HZ R32 193 2 4 H6 low pressure protection ...
Страница 194: ...AUX DC Inverter Free Match 50HZ R32 Cooling low pressure protection Heating low pressure protection ...
Страница 195: ...AUX DC Inverter Free Match 50HZ R32 195 2 5 P5 High exhaust temperature protection ...
Страница 196: ...AUX DC Inverter Free Match 50HZ R32 Cooling exhaust temperature protection ...
Страница 197: ...AUX DC Inverter Free Match 50HZ R32 197 Heating exhaust temperature protection ...
Страница 198: ...AUX DC Inverter Free Match 50HZ R32 2 6 H8 four way valve failure protection ...
Страница 199: ...AUX DC Inverter Free Match 50HZ R32 199 2 7 Sensor failure protection ...