Preparing for Commissioning
Installation & Commissioning Handbook, User Guide, AutroSafe Interactive Fire Alarm System, P-BSL330/IE,
Autronica Fire and Security AS
Page 13
3.5 Setting Parameters / Configuration Program
The parameter settings for Port 1
(AutroSafe)
and Port 2
(PLC)
are
done by means of the KD485 Configuration Program, which is
delivered with the BSL-330 module.
•
Make sure that the BSL-330 module is in Executive Mode. The
EXE indicator should be blinking rapidly. If not, communication is
not established, and you must repeat the procedure described in
the previous section (
Entering Executive Mode)
.
•
Insert the floppy disc into your harddisk drive.
•
Dobbelclick on the installation icon, and the Configuration Menu will
appear on screen.
•
Set the baud rate for Port 1
(AutroSafe)
to 9 600 baud, 8 bits,
1 stopbit, even parity (which is the default setup of AutroSafe).
Note that these parameters can be changed for AutroSafe by
means of the AutroSafe Configuration Tool.
•
Choose RX Xon/Xoff
disabled
(the Xon/Xoff characters to control
data being received on Port 1)
•
Choose TX Xon/Xoff
disabled
(the Xon/Xoff characters received by
BSL-330 control transmitted data on Port 1).
•
Set the appropriate parameters for Port 2 (external PLC
equipment) according to the PLC requirement.
•
Click on the highlighted button marked
Update KD485
and the
message
Writing new KD485 Configuration
will appear on screen.
When the message disappears, and the
Update KD485
button no
longer is highlighted, all parameters have been set and the
configuration is completed.