Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev . E, 2013-08-13, P/N 95-8625-17 .1, Rev: 2/13
Autronica Fire and Security AS
Page A-10
FM Approval and Performance Report – Continued
NOTE
FM Approvals minimum requirements are
response distance measurements at 0° (on
axis) and the limits of the field of view. These
high resolution field of view diagrams show the
measured response distances at all the indicated
angles in the horizontal plane.
0°
15°
30°
45°
15°
30°
45°
100 (30.5)
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
n-Heptane
at
Medium
Sensitivity (1 x 1 foot)
Field of View at Indicated Distance in Feet (m) for
Methane
at
Medium
Sensitivity (30 inch plume)
0°
15°
15°
30°
45°
30°
45°
65 ( 19.8)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
Methanol
at
Medium
Sensitivity (1 x 1 foot)
0°
15°
15°
30°
45°
30°
45°
70
(21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
0°
15°
30°
45°
15°
30°
45°
100 (30.5)
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
Field of View at Indicated Distance in Feet (m) for
JP-5
at
Medium
Sensitivity (2 x 2 foot)
0°
15°
30°
45°
15°
30°
45°
85 (25.9)
80 (24.4)
75 (22.9)
65 (19.8)
55 (16.8)
45 (13.7)
35 (10.7)
25 (7.6)
15 (4.6)
5 (1.5)
Field of View at Indicated Distance in Feet (m) for
Ethanol
at
Medium
Sensitivity (1 x 1 foot)
Field of View at Indicated Distance in Feet (m) for
Diesel
at
Medium
Sensitivity (1 x 1 foot)
0°
15°
15°
30°
45°
30°
45°
70
(21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)