Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev . E, 2013-08-13, P/N 95-8625-17 .1, Rev: 2/13
Autronica Fire and Security AS
Page A-2
FM Approval and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)
n-Heptane
1 x 1 foot
210 (64)*
11
n-Heptane**
1 x 1 foot
210 (64)*
6
n-Heptane
1 x 1 foot
100 (30.5)
3
n-Heptane
6 in. x 6 in.
80 (24.4)
3
Isopropanol
6 in. x 6 in.
70 (21 .3)
4
Diesel**
1 x 1 foot
150 (45.7)*
14
Ethanol
1 x 1 foot
210 (64)
11
Methanol
6 in. x 6 in.
40 (12 .2)
3
Methanol
1 x 1 foot
150 (45 .7)*
18
Methanol**
1 x 1 foot
150 (45 .7)*
7
Methane
30 inch plume
100 (30 .5)
3
JP-5**
1 x 1 foot
150 (45 .7)*
2
JP-5**
2 x 2 feet
210 (64)*
4
JP-5**
2 x 2 feet
100 (30 .5)
2
Office Paper 0.5 lb.
19" x 19" x 8"
100 (30 .5)
4
Corrugated Panel
18" x 36"
100 (30 .5)
8
* Outdoor test condition .
** Pre-burn from ignition .
Medium Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)
n-Heptane
1 x 1 foot
100 (30 .5)
12
n-Heptane
1 x 1 foot
50 (15 .2)
2
Diesel**
1 x 1 foot
70 (21 .3)
4
Ethanol
1 x 1 foot
85 (25.9)
13
Methanol
1 x 1 foot
70 (21 .3)
10
Methane
30 inch plume
65 (19 .8)
3
Methane
30 inch plume
55 (16 .8)
2
JP-5**
2 x 2 feet
100 (30 .5)
3
Office Paper 0.5 lb.
19" x 19" x 8"
50 (15 .2)
6
Corrugated Panel
18" x 36"
50 (15 .2)
2
** Pre-burn from ignition .
Low Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)
n-Heptane
1 x 1 foot
50 (15 .2)
10
Methanol
1 x 1 foot
20 (6 .1)
10
Methane
32 inch plume
15 (4 .6)
9
T-Low Sensitivity
Fuel
Size
Distance feet (m)
Average Response Time (seconds)
n-Heptane
1 x 1 foot
50 (15 .2)
7
Methanol
1 x 1 foot
20 (6 .1)
5
Methane
32 inch plume
15 (4 .6)
4